Modules<br />

Digital input/output (standard)<br />

PSSu K S 8DI 8DO 0.5(-T)<br />

Notice<br />

][Wichtig_PDB<br />

This data sheet is only intended for use<br />

during configuration. Please refer to<br />

the operating manual for installation<br />

and operation.<br />

][Technische Daten PSSu Digitale E/A/K<br />

Technical details<br />

3.4<br />

Application range<br />

Standard<br />

Module's device code<br />

0630h<br />

Number of ST input bits 8<br />

Number of ST output bits 8<br />

Support in system environment A<br />

from ST firmware version for other head modules 17<br />

from ST firmware version PSSu H S PN 2<br />

from ST firmware version PSSu WR S IDN 9<br />

Support in system environment B<br />

from head module ST firmware version 1.2.0<br />

Electrical data<br />

Internal supply voltage (module supply)<br />

Supply voltage range of module supply<br />

4.8 - 5.4 V<br />

Module's current consumption<br />

45 mA<br />

Module's power consumption<br />

0.13 W<br />

Periphery's supply voltage (periphery supply)<br />

Voltage range<br />

16.8 - 30.0 V<br />

Module's current consumption with no load<br />

0 mA<br />

Module's power consumption with no load<br />

0.00 W<br />

Inputs<br />

Number 8<br />

Input voltage<br />

24 V DC<br />

Input current<br />

2.5 - 4.0 mA<br />

Min. threshold voltage when signal changes from “1” to “0” 11.0 V<br />

Max. threshold voltage when signal changes from “0” to “1” 12.0 V<br />

Potential isolation between input and voltage for the internal module<br />

yes<br />

bus<br />

Outputs<br />

Number of positive-switching single-pole semiconductor outputs 8<br />

Short circuit-proof<br />

yes<br />

Potential isolation between semiconductor output and input yes<br />

Potential isolation between output and voltage for the internal yes<br />

module bus<br />

Typ. output current at “1” signal and rated voltage of semiconductor<br />

0.50 A<br />

output<br />

Permitted current range<br />

0.00 - 0.62 A<br />

Max. pulsed current for t < 100 ms<br />

6 A<br />

Residual current at “0” signal<br />

0.02 mA<br />

Permitted loads<br />

inductive, capacitive, resistive<br />

Infeed for<br />

Outputs<br />

Voltage<br />

24 V, DC<br />

Voltage tolerance -30 %/+25 %<br />

Max. continuous current that the external power supply must provide<br />

10.0 A<br />

Max. unit fuse protection F1<br />

10 A<br />

Max. unit fuse protection F1 in according with UL508<br />

4 A<br />