NRIPower Systems Control & Dispatching Research CenterProject Title:Combined Overcurrent & Earth Fault Relay, Design &ConstructionDepartment: Electronics & ControlEmployer: Niroo Research InstituteProject Staff: ---Project Manager: B. AreziProject Code: PCNPN11Summary:The combined phase and neutral overcurrent relay is used for the selective short circuitand time overcurrent protection of radial feeders in distribution networks. This relay isalso used for feeder earth fault protection in isolated neutral network and networks withresistively earthed neutral.Both the overcurrent unit and the earth fault unit feature two stage: a high-set stage anda low-set stage.Technical Specifications:Energizing inputsRated Current In1A/5AThermal withstand capability- Continuously 4A/20A- For 1s 50A/250ARated frequency50HzPower SupplySupply VoltagePower Consumption underQuiescent/Operating condition90-125V…6w/8wLow-set over current stageI>Start current.Operation Characterisitic- definite time charactersticoperating time- inverse time characteristic accto BS 142 and IEC 255-4Time multiplier K0.05…2.00In0.05…100sExtremely InverseVery InverseNormal InverseLong time Inverse0.05…1.0086