12.07.2015 Views

Boiler Manual - Weil-McLain

Boiler Manual - Weil-McLain

Boiler Manual - Weil-McLain

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

GV90+ gas-fired water boiler — <strong>Boiler</strong> <strong>Manual</strong>DIRECT VENT — Vertical with separate pipesAllowable vent/air pipe materials &lengthsFigure 53 Separate pipes vertical terminationUse only the vent materials and kits listedin Figure 40, page 33. Provide pipe adaptersif specified.1. Locate the terminations such that the total air pipingand vent piping from the boiler to the terminationwill not exceed the maximum length given inFigure 39, page 32.Determine termination location1. The air and vent terminations must be installed asshown in Figure 53, page 43.2. The terminations must comply with clearances andlimitations shown in Figure 41, page 35.3. Locate the terminations so they are not likely to bedamaged by foreign objects, such as stones or balls,or subject to buildup of leaves or sediment.Multiple vent/air terminations (Figure 54)1. When terminating multiple GV90+ boilers, terminateeach vent/air connection as described inthis section.Terminate all vent pipes at the sameheight and all air pipes at the same heightto avoid possibility of severe personalinjury, death or substantial propertydamage.2. Place roof penetrations to obtain minimum clearanceof 12 inches between edge of air intake elbowand adjacent vent pipe of another boiler for U. S.installations (see Figure 54, page 44). For Canadianinstallations, provide clearances required by CSAB149.1 or B149.2 Installation Code.3. The air inlet of a GV90+ boiler is part of a directvent connection. It is not classified as a forced airintake with regard to spacing from adjacent boilervents.Prepare roof penetrations1. Air pipe penetration:a. Cut a hole for the air pipe. Size the air pipehole as close as desired to the air pipe outsidediameter.2. Vent pipe penetration:a. Cut a hole for the vent pipe. For either combustibleor noncombustible construction, size thevent pipe hole at least 0.4” larger than the ventpipe diameter (4” hole for 3” PVC).b. Insert a galvanized metal thimble in the ventpipe hole.Step 1 Read and follow all instructions in this manual. DO NOT proceedwith vent/air installation until you have read page 29through page 35.Step 2 Install the boiler in a location that allows proper routing of all ventand air piping to the selected sidewall location.Step 3 Make sure the selected vertical termination location complies withFigure 41, page 35. (Multiple boiler terminations must also complywith Figure 54, page 44.)Step 4 Use only the vent materials listed in Figure 40, page 33. Provide pipeadapters where required. Vent piping and air piping lengths must notexceed the values shown in Figure 39, page 32.Step 5 Prepare the vertical penetrations and secure penetration componentsas instructed in this section. See “Prepare roof penetrations” on page 43and “Termination and fittings” on page 44.Step 6 The air piping must terminate in a 180-degree return bend or downturnedelbow as shown above. The vent piping must terminate in acoupling pointed upward as shown above.Step 7 Install vent and air piping between the boiler and the vertical terminations.Slope horizontal piping downward toward the boiler at least 1/4inch per foot. Install pipe supports every 5 feet on both the horizontaland vertical runs. Install a hanger support within 6 inches of any upturnin the piping. See page 48 for general guidelines.Step 8 Insert the vent and air piping through the vertical penetrations andsecure the termination fittings.Step 9 Maintain clearances shown above. Vent and air terminations must befitted with a bird screen as shown.Part number 550-142-054/1211 43

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!