GV90+ gas-fired water boiler — <strong>Boiler</strong> <strong>Manual</strong>DIRECT EXHAUST — Sidewall (continued)b. Provide metal cover plates (item 2, Figure 62).The outer plate MUST provide a stop to preventthe vent elbow from being pushed inward. (SeeNOTICE at right.) Hole diameters in the metalplates must be 3 5 ⁄8” for PVC pipe. For AL29-4C vent pipe and coupling (or elbow) — sizehole large enough to clear vent pipe, but smallenough to prevent the coupling (or elbow) frombeing pushed through.The <strong>Weil</strong>-<strong>McLain</strong> sidewall termination kitsupplied with each boiler includes metalplates with two openings. These plates canbe trimmed and used for direct exhaustvent termination cover plates when thevent diameter used matches the hole sizein the plates provided with the boiler.c. Insert the galvanized metal thimble (by installer)in the vent pipe hole as shown in Figure 62.2. Follow all local codes for isolation of vent pipe whenpassing through floors or walls.Termination and fittings1. If using a coupling or elbow for the termination,prepare the vent termination fitting (Figure62, page 52) by inserting a bird screen. Birdscreens are not supplied with the GV90+ boiler.Purchase separately from <strong>Weil</strong>-<strong>McLain</strong>.2. You can install the vent termination using eitherof the configurations shown in Figure 61, page 51.3. Maintain the required dimensions of the finishedtermination piping as shown in Figure 61, page 51.4. Do not extend exposed vent pipe outside of thebuilding more than shown in this document. Condensatecould freeze and block vent pipe.Figure 62 DIRECT EXHAUST — Sidewall — termination assemblyand termination options — all parts by installer exceptwhere shown otherwise1 Vent piping2 Cover plates3 Galvanized thimble4 Vent termination elbow5 Bird screenLEGEND for Figure 626 Extend vent pipe through outside plate enough to attachtermination coupling (or elbow when snorkeled).7 Snorkel option (to elevate vent termination) — requires birdscreen8 Coupling option — requires bird screen9 <strong>Weil</strong>-<strong>McLain</strong> termination plate option (plate is supplied withboiler) — bird screen not required52Part number 550-142-054/1211

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!