12.07.2015 Views

Boiler Manual - Weil-McLain

Boiler Manual - Weil-McLain

Boiler Manual - Weil-McLain

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

GV90+ gas-fired water boiler — <strong>Boiler</strong> <strong>Manual</strong>DIRECT EXHAUST — <strong>Boiler</strong> room air openingsCombustion air provisionThe GV90+ boiler can use inside air if no contaminants are present in theboiler space. (If contaminants are likely to be present, install the boileras a direct vent appliance, using the appropriate vent instructions in thismanual.)The boiler room must be fitted with combustion air openings large enoughto provide air for all appliances in the room. Use the following informationto size the openings. Ensure the installation complies with all applicablecodes and standards.Where the GV90+ boiler shares a space with other appliances, the combustionair openings must be sized to handle the combined requirements ofall appliances in the space.Sizing combustion air openingsAir openings provide for ventilation (as well as combustion air) to preventoverheating of the boiler controls and boiler space. Air is also needed forother appliances located in the same space.Use Figure 60, page 50, selecting the appropriate installation conditions.Air openings must be sized to handle all appliances and airmovers (exhaust fans, etc.) using the air supply.The sizing given in Figure 60, page 50 is based on the National Fuel GasCode, ANSI Z223.1, allowing adequate air openings for gravity-vented gasappliances (Category I) in addition to that needed for the GV90+ boiler.The air openings recommended in Figure 60, page 50 will allow adequateventilation and combustion air provided the boiler room is not subjectedto negative pressure due to exhaust fans or other mechanical ventilationdevices.Refer to the National Fuel Gas Code for dealing with other conditions.Free area — louver allowanceThe free area of openings means the area after reduction for any installedlouvers or grilles. Be sure to consider this reduction when sizing the airopenings.Special considerationsTight constructionANSI Z223.1 defines unusually tight constructionwhere:1. Walls and ceilings exposed to the outside atmospherehave a continuous water vapor retarder witha rating of 1 perm or less with openings gasketed,and . . .2. Weather-stripping has been added on openablewindows and doors, and . . .3. Caulking or sealants are applied to areas such asjoints around windows and door frames, betweensole plates and floors, between wall-ceiling joints,between wall panels, at penetrations for plumbing,electrical, and gas lines, and in other openings.For buildings with such construction, provide airopenings into the building from outside, sized per theappropriate case in Figure 60, page 50 if appliances areto use inside air for combustion and ventilation.Exhaust fans and air moversThe appliance space must never be under a negativepressure unless all appliances are installed as directvent. Always provide air openings sized not only tothe dimensions required for the firing rate of all appliances,but also to handle the air movement rate of theexhaust fans or air movers using air from the buildingor space.Motorized air dampersIf the air openings are fitted with motorized dampers,electrically interlock the damper to:• Prevent the boiler from firing if the damper is notfully open.• Shut the boiler down should the damper close duringboiler operation.To accomplish this interlock, wire an isolated contact(proving the damper open) in series with the thermostatinput to the boiler. The boiler will not start if thiscontact is open, and will shut down should it openduring operation.Part number 550-142-054/1211 49

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!