11kV LA11kV LINELAS1.2.3.NOTESTHE LAYOUT AS SHOWN ENV ISAGES THE USE OF 11kVVACUUM CIRCUIT BREAKERS (REC SPEC. 22/1983).WHICH SHALL NOT REQUIRE ISOLATING SWITCHES ASTHEIR INTEGRAL PART AS PARTICULARLY NOM AINTENANCE IS NEEDED ON THESE BREAKERS AND ITWILL ALSO ECONOMISE IN THE COST.CONDUCTORS USED FOR 11k V JUM PERS AND BUSBARSSHALL NOT BE LESS THAN 50 SQ.MM. (C.E.) ACSR.THE SUPPORTS SHALL NOT BE CYDED BUT MAY BESUITABLY CONCRETED33/11kV P.Tf VCB FDR VCB125004000 450011kV LA11 kVVCB11kV11kV11kV/0.433kVSTATION TRANSFORMERFig. 12.2: 12 kV Outdoor Switchyard with Pole Structure – REC Standard layout2-20