to earthxvii. Difference in the instant ofclosing/opening of contacts of all the 3polea) Openingb) Closingxviii Small inductive current interruptingcapacityxix.Whether breaker suitable <strong>for</strong> single poleoperation or gang operation of threepolesNot more than 3.33 ms.Not more than 5 ms.Any value upto 10Awith out switching overvoltage exceeding 2.0p.u.Gang operation of threepoles throughmechanical linkagesxx. Number of trip coils Two Nos. per breaker4-22