MICROMASTERMICROMASTER VectorMIDIMASTER VectorStandard ApplicationsParameter settings for this application which are changed from their defaults:Note that P009 must be set to 2 or 3 before parameter numbers above P009 can be modified.Number Value MeaningP002 3.00 Ramp Up time 3.0 secondsP003 3.00 Ramp Down time 3.0 secondsP006 1 Analogue setpoint controlP007 0 Front panel keys disabledP015 1 Automatic start on power up if run switch is enabledP016 3 Flying Start in forward direction enabledP021 25.00 Minimum analogue setpoint 25%P022 50.00 Maximum analogue setpoint 50%P026 2 Analogue output 2 indicates motor currentP052 10 Din2 used to reset drive faultP062 1 Relay output 2 indicates drive runningP077 2 Quadratic V/F curve selectedP080 0.83 Motor rating plate power factor = 0.83P082 1460 Motor rating plate speed = 1460 RPMP083 21.9 Motor rating plate current = 21.9 AP201 1 PID closed loop control enabledP202 0.2 Proportional Gain coefficient 0.2P203 0.05 Integral Gain coefficient 0.05P207 10 Integral error is cleared if the error between setpoint and feedback>10%P211 25.00 0 setpoint corresponds to 25%P212 50.00 Full setpoint corresponds to 50%P323 1 Analogue input 2 (PID input) configured for 4 – 20 mAThe motor rating plate parameters correspond to a 1LA7 11 kW 4 pole motor connected in Star.(11kW)Siemens DA 64 – 1998/99 (04/99) 4/11