248 <strong>Practical</strong> Modern <strong>SCADA</strong> Protocols: DNP3, <strong>60870</strong>.5 <strong>and</strong> <strong>Related</strong> <strong>Systems</strong><br />

Valid cause of transmission codes<br />

Background scan<br />

Spontaneous<br />

Requested<br />

Return of information caused by remote comm<strong>and</strong><br />

Return of information caused by local comm<strong>and</strong><br />

Interrogated by station interrogation<br />

Interrogated by group G interrogation, G= <br />

Notes<br />

NVA – Normalized value<br />

Types 10, 34 Measured, normalized value with time<br />

INFORMATION OBJECT TYPE: 10, 34<br />

CODE:<br />

M_ME_TA_1, M_ME_TD_1<br />

DESCRIPTION:<br />

Measured value, normalized value with time<br />

tag<br />

VALID WITH SQ: 0<br />

Information Object for SQ = 0 (Sequence of Information Objects)<br />

Information Object Address<br />

Value<br />

Value<br />

NVA – Normalized Value<br />

IV NT SB BL OV QDS – Quality Descriptor<br />

CP24Time2a or CP56Time2a Three or seven-octet binary time<br />

Valid cause of transmission codes<br />

Spontaneous<br />

Requested<br />

Notes<br />

NVA – Normalized value<br />

Type 10 has three-octet time. Type 34 has seven-octet time