Applications of DNP3 <strong>and</strong> <strong>SCADA</strong> <strong>protocols</strong> 385<br />

DNP3 events<br />

In order to minimize network congestion, consecutive messages are inhibited for a set<br />

time to allow other devices to use the network (Min Unsol Event Tx Delay). When an<br />

event happens at a site, this will often trigger a series of other events, so a short time delay<br />

can also be set to allow all changes to be included in the one transmission (Notification<br />

Event Delay).<br />

The event object type that will be used by the RTU in RBE messages to the DNP3<br />

master can be defined for each data type.<br />

Some DNP3 masters can process multiple analog events for the same point, however<br />

analog event buffer mode can be set to single if the master station does not permit this.<br />

If no triggered events occur <strong>and</strong> the buffered events accumulate, they will eventually<br />

cause an unsolicited message to the master when the number of events reaches Class x<br />

Min Events.<br />

Each class can be individually enabled or disabled by the DNP3 master station.