472 <strong>Practical</strong> Modern <strong>SCADA</strong> Protocols: DNP3, <strong>60870</strong>.5 <strong>and</strong> <strong>Related</strong> <strong>Systems</strong><br />

3.1.1.1.8 Type 100<br />

INFORMATION OBJECT TYPE: 100<br />

CODE:<br />

C_IC_NA_1<br />

DESCRIPTION:<br />

Interrogation Comm<strong>and</strong><br />

VALID WITH SQ: 0<br />

Information Object for SQ = 0 (Sequence of Information Objects)<br />

Information Object Address<br />

QOI – Qualfier of Interrogation<br />

Valid Cause of Transmission Codes<br />

Activation<br />

Activation Confirmation<br />

Deactivation<br />

Deactivation Confirmation<br />

Activation Termination<br />

3.1.1.1.9 Type 103<br />

INFORMATION OBJECT TYPE: 103<br />

CODE:<br />

C_CS_NA_1<br />

DESCRIPTION:<br />

Clock synchronisation comm<strong>and</strong><br />

VALID WITH SQ: 0<br />

Information Object for SQ = 0 (Sequence of Information Objects)<br />

Information Object Address<br />

CP56Time2a<br />

Seven Octet Binary Time<br />

(date <strong>and</strong> Clock time in milliseconds)<br />

Valid Cause of Transmission Codes<br />

Spontaneous<br />

Activation<br />

Activation Confirmation