02.02.2018 Views

Practical_modern_SCADA_protocols_-_dnp3,_60870-5_and_Related_Systems

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

476 <strong>Practical</strong> Modern <strong>SCADA</strong> Protocols: DNP3, <strong>60870</strong>.5 <strong>and</strong> <strong>Related</strong> <strong>Systems</strong><br />

Interpretation:<br />

Case<br />

Interpretation<br />

F=, E= Value = <br />

F non-zero, E=<br />

Non-normalised number Value = (-1) S x 2 E-126 x (0.F)<br />

F non-zero, E Normalised number Value = (-1) S x 2 E-127 x (1.F)<br />

F=, E=<br />

Value = (-1) S x infinity<br />

F non-zero, E= Not a valid number<br />

Note that a normalised number is one in which has been scaled to the form 0.1xxxx so that<br />

it falls between 0.1 <strong>and</strong> 1.0, <strong>and</strong> then multiplied by 2 to give 1.xxxx. This removes the<br />

leading ‘1’ to the right of the radix point, which is redundant because it is always a 1.<br />

BCR<br />

Binary counter reading<br />

7 6 5 4 3 2 1 0<br />

Octet 1 7 0<br />

Octet 2 15 8<br />

Octet 3 23<br />

Counter I32<br />

16<br />

Octet 4 31 24<br />

Octet 5 IV CA CY SQ<br />

Key<br />

I32 Counter value I32[0..31] <br />

SQ Sequence number UI5[32..36] <br />

CY Carry<br />

CA Counter adjusted<br />

IV Counter valid<br />

SCO<br />

Single comm<strong>and</strong><br />

This is a comm<strong>and</strong> to operate a single output. Bits 2 to 7 are the Qualifier of Comm<strong>and</strong><br />

sub-field. This is used for other comm<strong>and</strong>s also.

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!