468 <strong>Practical</strong> Modern <strong>SCADA</strong> Protocols: DNP3, <strong>60870</strong>.5 <strong>and</strong> <strong>Related</strong> <strong>Systems</strong><br />

Type 2<br />

INFORMATION OBJECT TYPE: 2<br />

CODE:<br />

M_SP_TA_1<br />

DESCRIPTION:<br />

Single-point information with time tag<br />

VALID WITH SQ: 0<br />

Information Object for SQ = 0 (Sequence of Information Objects)<br />

Information Object Address<br />

IV NT SB BL SP SIQ<br />

I<br />

CP24Time2a<br />

Three-octet binary time<br />

Valid Cause of Transmission Codes<br />

Spontaneous<br />

Requested<br />

Return of information caused by remote comm<strong>and</strong><br />

Return of information caused by local comm<strong>and</strong><br />

Notes<br />

SIQ – Single-point information with quality descriptor.<br />

3.1.1.1.4 Type 3<br />

INFORMATION OBJECT TYPE: 3<br />

CODE:<br />

M_DP_NA_1<br />

DESCRIPTION:<br />

Double-point information without time tag<br />

VALID WITH SQ: 0, 1<br />

Information Object for SQ = 0 (Sequence of Information Objects)<br />

Information Object Address<br />

IV NT SB BL DPI DIQ – Double Point with quality<br />

Information Object for SQ = 1 (Sequence of Information Elements)<br />

Information Object Address<br />

IV NT SB BL DPI DIQ, Information Element 1<br />

IV NT SB BL DPI DIQ, Information Element N