478 <strong>Practical</strong> Modern <strong>SCADA</strong> Protocols: DNP3, <strong>60870</strong>.5 <strong>and</strong> <strong>Related</strong> <strong>Systems</strong><br />

CP24Time2a – Three Octet Binary Time<br />

This is typically used for time tags of information objects. It is the first three octets of the<br />

seven octet binary time element.<br />

7 6 5 4 3 2 1 0 Octet Range<br />

Milliseconds ms<br />

1<br />

2<br />

0 .. 59,999 ms<br />

Minutes 3 0 .. 59 min<br />

CP16Time2a – Two Octet Binary Time<br />

This is used for elapsed times such as for relay operating time. It is the first two octets of<br />

the seven octet binary time element.<br />

7 6 5 4 3 2 1 0 Octet Range<br />

1<br />

Milliseconds ms<br />

2<br />

0 .. 59,999 ms<br />

QOI Qualifier of Interrogation<br />

7 6 5 4 3 2 1 0<br />

QOI<br />

Key<br />

QOI Qualifier of comm<strong>and</strong> UI8[1..7] <br />

= Not used<br />

= Reserved for future st<strong>and</strong>ard definitions<br />

= Station interrogation – global<br />

= Interrogation of group G, where G = <br />

= Reserved for future st<strong>and</strong>ard definitions<br />

= Reserved for special use (private range)