254 <strong>Practical</strong> Modern <strong>SCADA</strong> Protocols: DNP3, <strong>60870</strong>.5 <strong>and</strong> <strong>Related</strong> <strong>Systems</strong><br />

Types 16, 37 Integrated totals with time<br />

INFORMATION OBJECT TYPE: 16,37<br />

CODE:<br />

M_IT_TA_1, M_IT_TB_1<br />

DESCRIPTION:<br />

Integrated totals with time tag<br />

VALID WITH SQ: 0<br />

Information Object for SQ = 0 (Sequence of Information Objects)<br />

Information Object Address<br />

S<br />

IV CA CY<br />

Value<br />

Value<br />

Value<br />

Value<br />

Sequence Number<br />

BCR – Binary Counter Reading<br />

CP24Time2a or CP56Time2a<br />

Three or seven-octet binary time<br />

Valid cause of transmission codes<br />

Spontaneous<br />

Requested by general counter request<br />

Requested by group G counter request G = <br />

Notes<br />

BCR – Binary counter reading<br />

Type 16 has three-octet time. Type 37 has seven-octet time<br />

Types 17, 38 Event of protection with time<br />

INFORMATION OBJECT TYPE: 17, 38<br />

CODE:<br />

M_EP_TA_1, M_EP_TD_1<br />

DESCRIPTION:<br />

Event of protection equipment with time tag<br />

VALID WITH SQ: 0<br />

Information Object for SQ = 0 (Sequence of Information Objects)<br />

Information Object Address<br />

IV NT SB BL EI ES SEP<br />

CP16Time2a<br />

Two-octet binary time, elapsed time<br />

CP24Time2a or CP56Time2a<br />

Three or seven-octet binary time