Elevated or<br />
Pressurized<br />
Return<br />
P 2<br />
Steam<br />
S<strong>up</strong>ply<br />
Steam Trap Station<br />
Float &<br />
Thermostatic<br />
Steam Trap<br />
Thermo-<br />
Dynamic<br />
Steam Trap<br />
Spira-tec<br />
Loss Detector<br />
Strainer<br />
Spira-tec<br />
Loss Detector<br />
See Fig. II-35A for<br />
the preassembled<br />
Process Condensate<br />
Removal Module<br />
Strainer<br />
Moisture<br />
Separator<br />
Motive<br />
Steam S<strong>up</strong>ply<br />
Float &<br />
Thermostatic<br />
Steam Trap<br />
Drain to<br />
Safe<br />
Place<br />
Pressure<br />
Powered<br />
Pump<br />
Figure II-34A<br />
Condensate Recovery Module<br />
A preassembled modular pumping system can be used<br />
to recover and reuse the condensate.<br />
Strainer<br />
Thermo<br />
-static<br />
Air Vent<br />
Reservoir Pipe<br />
Pneumatic<br />
Control<br />
Valve<br />
Heat Exchanger<br />
Liquid Expansion<br />
Steam Trap<br />
Drain<br />
P 1<br />
Control<br />
Signal<br />
Controller<br />
S<strong>up</strong>ply<br />
Air<br />
Note: To prevent<br />
overheating,<br />
the scensor<br />
must not see<br />
a “dead” flow.<br />
Sensor<br />
Hot<br />
Flow<br />
Cool<br />
Return<br />
Figure II-35<br />
Draining Equipment to Pressurized<br />
Return with Closed Loop<br />
Pump/Trap Drainage System<br />
P1 exceeds P2 except when partial<br />
loads “stall” the exchanger. With this<br />
hook <strong>up</strong>, the reservoir pipe is always<br />
connected to, and at the same pressure<br />
as, the heat exchanger steam<br />
space. Condensate drains to it freely.<br />
The pump body is connected in the<br />
same way, except during the discharge<br />
stroke when the inlet check valve and<br />
the exhaust valve are closed. After discharge,<br />
the residual steam in the pump<br />
body is exhausted to the heater and its<br />
latent heat can then be recovered.<br />
Steam trap functions at full load and<br />
Thermoton drains at shutdown.<br />
Figure II-35A<br />
Process Condensate Removal Module<br />
A preassembled modular will remove condensate from the<br />
heat exchanger under all operating conditions.<br />
HOOK-UP DIAGRAMS<br />
101