HOOK-UP DIAGRAMS<br />

102<br />

Figure II-36<br />

Low Pressure Steam Absorption Chiller<br />

To<br />

Condensate<br />

Return<br />

Thermo-<br />

Dynamic<br />

Steam Trap<br />

with Integral<br />

Strainer<br />

Float &<br />

Thermostatic<br />

Steam Trap<br />

Pressure<br />

Powered<br />

Pump<br />

Figure II-37<br />

High Pressure Steam Absorption Chiller<br />

To<br />

Condensate<br />

Return<br />

Packaged<br />

Pressure<br />

Powered<br />

Pump<br />

Motive<br />

Steam S<strong>up</strong>ply<br />

Vent<br />

Drain to<br />

Safe Place<br />

Motive<br />

Steam S<strong>up</strong>ply<br />

Check<br />

Valve<br />

Reservoir Pipe<br />

Thermo-Dynamic<br />

Steam Trap<br />

with Integral<br />

Strainer<br />

Thermostatic<br />

Air Vent<br />

Absorption<br />

Chiller<br />

Absorption Chiller<br />

Steam S<strong>up</strong>ply<br />

(15 psig or less)<br />

Steam S<strong>up</strong>ply<br />

(normally 45<br />

psig or higher)<br />

Note: Depending on chiller manufacturer, a steam trap<br />

may not be required or it may be s<strong>up</strong>plied with the chiller.<br />

Other specialties needed may include a steam pressure<br />

reducing valve on the inlet, steam separator with trap,<br />

steam safety valve or inlet strainer.