03.03.2013 Views

2000 Hook-up Book - Spirax Sarco

2000 Hook-up Book - Spirax Sarco

2000 Hook-up Book - Spirax Sarco

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

SYSTEM DESIGN<br />

22<br />

Parallel and Series Operation of Reducing Valves<br />

This can be clarified by an<br />

example. S<strong>up</strong>pose that a maximum<br />

load of 5,000 lb/h at 30 psi<br />

can be s<strong>up</strong>plied through one<br />

valve capable of passing 4,000<br />

lb/h and a parallel valve capable<br />

of 1,300 lb/h. One valve is set at<br />

29 psi and the other at 31 psi. If<br />

the smaller valve is the one set at<br />

31 psi, this valve is used to meet<br />

loads from zero <strong>up</strong> to 1,300 lb/h<br />

with a controlled pressure at<br />

approximately 31 psi. At greater<br />

loads, the controlled pressure<br />

drops to 29 psi and the larger<br />

valve opens, until eventually it is<br />

passing 3,700 lb/h to add to the<br />

1,300 lb/h coming through the<br />

smaller valve for a total of 5,000<br />

lb/h.<br />

There may be applications<br />

where the load does not normally<br />

fall below the minimum capacity<br />

of the larger valve. It would then<br />

be quite normal to set the 4,000<br />

lb/h valve at 31 psi and to s<strong>up</strong>plement<br />

the flow through the 1,300<br />

lb/h valve at 29 psi in those few<br />

occasions when the extra capacity<br />

was required.<br />

Sometimes the split between<br />

the loads is effectively unknown.<br />

It is usual then to simply select<br />

valves with capacities of 1/3 and<br />

2/3 of the maximum with the<br />

smaller valve at the slightly higher<br />

pressure and the larger one at<br />

the slightly lower pressure.<br />

Two-Stage<br />

or Series Operation<br />

Where the total reduction in pressure<br />

is through a ratio of more than<br />

10 to 1, consideration should be<br />

given to using two valves in series,<br />

Fig. 39 (page 20). Much will depend<br />

on the valves being used, on the<br />

total pressure reduction needed<br />

and the variations in the load. Pilot<br />

Operated controls have been used<br />

successfully with a pressure turndown<br />

ratio as great as 20 to 1, and<br />

could perhaps be used on a fairly<br />

steady load from 100 psig to 5 psi.<br />

The same valve would probably be<br />

unstable on a variable load, reducing<br />

from 40 to 2 psi.<br />

There is no hard and fast<br />

rule, but two valves in series will<br />

usually provide more accurate<br />

control. The second, or Low<br />

Pressure valve, should give the<br />

“fine control” with a modest turndown,<br />

with due consideration<br />

being given to valve sizes and<br />

capacities. A practical approach<br />

when selecting the turndown of<br />

each valve, that results in smallest<br />

most economical valves, is to<br />

avoid having a non-critical drop in<br />

the final valve, and stay close to<br />

the recommended 10 to 1 turndown.<br />

Series Installations<br />

For correct operation of the<br />

valves, some volume between<br />

them is needed if stability is to be<br />

achieved. A length of 50 pipe<br />

diameters of the appropriately<br />

sized pipe for the intermediate<br />

pressure, or the equivalent volume<br />

of larger diameter pipe is<br />

often recommended.<br />

It is important that the downstream<br />

pressure sensing pipes<br />

are connected to a straight section<br />

of pipe 10 diameters<br />

downstream from the nearest<br />

elbow, tee, valve or other obstruction.<br />

This sensing line should be<br />

pitched to drain away from the<br />

pressure pilot. If it is not possible<br />

to arrange for this and to still connect<br />

into the top of the<br />

downstream pipe, the sensing<br />

line can often be connected to the<br />

side of the pipe instead.<br />

Equally, the pipe between the<br />

two reducing valves should<br />

always be drained through a<br />

stream trap, just as any riser<br />

downstream of the pressure<br />

reducing station should be<br />

drained. The same applies where<br />

a pressure reducing valve s<strong>up</strong>plies<br />

a control valve, and it is<br />

essential that the connecting pipe<br />

is drained <strong>up</strong>stream of the control<br />

valve.<br />

Bypasses<br />

The use of bypass lines and<br />

valves should usually be avoided.<br />

Where they are fitted, the capacity<br />

through the bypass should be<br />

added to that through the wide<br />

open reducing valve when sizing<br />

relief valves. Bypass valves are<br />

often found to be leaking steam<br />

because of wiredrawing of the<br />

seating faces when valves have<br />

not been closed tightly.<br />

If a genuine need exists for a<br />

bypass because it is essential to<br />

maintain the s<strong>up</strong>ply of steam,<br />

even when a reducing valve has<br />

developed some fault or is undergoing<br />

maintenance, consideration<br />

should be given to fitting a<br />

reducing valve in the bypass line.<br />

Sometimes the use of a parallel<br />

reducing station of itself avoids<br />

the need for bypasses.<br />

Back Pressure Controls<br />

A Back Pressure regulator or surplussing<br />

valve is a derivative of a<br />

pressure reducing valve, incorporating<br />

a reverse acting pilot valve.<br />

The pressure sensing pipe is connected<br />

to the inlet piping so that the<br />

pilot valve responds to <strong>up</strong>stream<br />

pressure. Any increase in <strong>up</strong>stream<br />

pressure then opens the reverse<br />

acting pilot valve, causing the main<br />

valve to open, while a fall below the<br />

set pressure causes the main valve<br />

to close down, Fig. II-18 (page 92).<br />

These controls are useful in<br />

flash steam recovery applications<br />

when the s<strong>up</strong>ply of flash steam<br />

may at times exceed the demand<br />

for it. The BP control can then surplus<br />

to atmosphere any excess<br />

steam tending to increase the<br />

pressure within the flash steam<br />

recovery system, and maintains<br />

the recovery pressure at the<br />

required level.<br />

The control is also useful in<br />

eliminating non-essential loads in<br />

any system that suffers undercapacity<br />

at peak load times,<br />

leaving essential loads on line.<br />

Back Pressure Controls are<br />

not Safety Valves and must never<br />

be used to replace them.

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!