SYSTEM DESIGN<br />

54<br />

Clean Steam<br />

Figure 59<br />

Effective Condensate Drainage<br />

Process/<br />

Medium<br />

Process<br />

Trap<br />

Drip<br />

Trap<br />

Steam<br />

Inlet<br />

A hospital was experiencing continuing problems with a<br />

number of its sterilizers which were having an adverse<br />

effect on both the sterilization process itself and the<br />

amount of maintenance required to keep the units in service.<br />

These problems included:<br />

• Ineffective sterilization<br />

• Prolonged sterilization cycles<br />

• Wet and discolored packs<br />

• Instrument stains, spotting and rusting<br />

• High maintenance of drain traps and controls<br />

• Dirty sterilizer chambers requiring frequent cleaning<br />

Solution<br />

In discussion with the hospital maintenance engineer, the<br />

<strong>Spirax</strong> <strong>Sarco</strong> Sales Representative offered the opinion<br />

that these problems were a result of a wet and contaminated<br />

steam s<strong>up</strong>ply. In a number of cases the steam<br />

s<strong>up</strong>ply to the sterilizers was unconditioned, allowing moisture<br />

and solid particles, such as pipe scale and rust, to<br />

enter both the sterilizer jacket and chamber, resulting in the<br />

problems identified by the user.<br />

The solution was to install <strong>Spirax</strong> <strong>Sarco</strong> steam filter<br />

stations. Each steam filter station is comprised of:<br />

• An isolation valve to aid in maintenance.<br />

• A separator complete with strainer and drain trap to<br />

remove residual condensate and any entrained moisture<br />

being carried in suspension within the steam.<br />

• A main line strainer to remove larger solid particles.<br />

• A steam filter and drain trap combination.<br />

Table 15: Saturated Steam Capacities — OD Tube Capacities in lb/h<br />

Tube Size (O.D. x 0.065 inch wall)<br />

Pressure Velocity<br />

psi ft/sec 1 /4" 3 /8" 1 /2" 3 /4" 1 1 1 /2" 2" 1 2 /2" 3"<br />

50 — — 5 20 35 90 170 270 395<br />

5 80 — 5 10 30 60 145 270 430 635<br />

120 — 5 15 45 85 215 405 650 950<br />

50 — 5 10 25 45 110 210 335 490<br />

10 80 — 5 15 35 70 180 330 535 785<br />

120 — 10 20 55 110 270 500 800 1175<br />

50 — 5 10 30 60 155 285 460 675<br />

20 80 — 10 20 50 100 245 460 735 1080<br />

120 5 10 25 75 150 370 685 1105 1620<br />

50 — 5 15 40 80 195 365 585 855<br />

30 80 5 10 30 65 125 310 580 935 1370<br />

120 5 15 35 95 190 465 870 1400 2050<br />

50 — 10 15 50 95 235 440 705 1035<br />

40 80 5 10 25 75 150 375 700 1125 1655<br />

120 5 20 40 115 230 556 1050 1690 2480<br />

50 — 10 20 55 110 275 515 825 1210<br />

50 80 5 15 30 90 180 440 820 1320 1935<br />

120 5 20 50 135 265 660 1235 1980 2905<br />

50 — 10 25 65 125 315 590 945 1385<br />

60 80 5 15 35 105 205 505 940 1510 2215<br />

120 5 25 55 155 305 755 1411 2265 3325<br />

50 5 15 30 80 160 395 735 1180 1730<br />

80 80 5 20 45 130 255 630 1175 1890 2770<br />

120 5 30 70 195 380 950 1764 2835 4155<br />

50 5 15 35 95 190 470 880 1415 2075<br />

100 80 5 25 55 155 305 755 1410 2265 3320<br />

120 10 35 85 230 455 1135 2115 3395 4975<br />

50 5 20 40 115 220 550 1030 1650 2420<br />

120 80 5 30 65 180 355 885 1645 2640 3875<br />

120 10 40 95 270 535 1325 2465 3965 5810<br />

Case in Action: Hospital Sterilizer<br />

The steam filter specified was a <strong>Spirax</strong> <strong>Sarco</strong> CSF16<br />

fitted with a 1 micron absolute filter element. The cleanable<br />

CSF16 filter element ensured that 99% of all particles larger<br />

than 0.1 microns were removed, while the thermostatic<br />

steam trap drained any condensate that formed in the filter<br />

body during operation and periods when the steam s<strong>up</strong>ply<br />

to the sterilizer was isolated. These installations resulted in<br />

steam s<strong>up</strong>plies free of both moisture and solid particles.<br />

Benefits<br />

• Effective sterilization every time<br />

• Reduced sterilization cycles and improved productivity<br />

• High quality of packs and instruments without spots,<br />

stains or corrosion<br />

• Minimal re-work of sterilizer loads<br />

• Reduced cleaning and maintenance of sterilizer, drain<br />

traps and controls<br />

Cost Savings<br />

With the help of the hospital maintenance engineer, a<br />

steam filter station payback analysis sheet was completed.<br />

The estimated cost of maintenance, the cost associated<br />

with re-working wet or spotted packs, and the cost due to<br />

loss of performance were included in the payback calculation.<br />

In total, annual costs were over $25,000 for each<br />

sterilizer. Using this figure a payback period of less than<br />

two months was established for suitably sized <strong>Spirax</strong> <strong>Sarco</strong><br />

steam filter stations.