Fans<br />

G600 Media Gateway<br />

Three 12-volt DC variable-speed fans cooling <strong>for</strong> the G600 Media Gateway. The fans are<br />

integrated into the back of the cabinet. The fans pull air through the front <strong>and</strong> the left side <strong>and</strong><br />

up through the cabinet. Air exits from the back of the cabinet. The 650A Global Power supply<br />

controls the speed of the fans. The 650A Global Power supply varies the fan input voltage<br />

between 8 VDC <strong>and</strong> 14 VDC, depending on a temperature sensor that is mounted in the power<br />

supply, <strong>and</strong> adjusts each fan’s operating speed accordingly<br />

The fan assembly includes the three fans, a base plate to which the fans are attached, wiring,<br />

<strong>and</strong> an AMP connector. The AMP connector plugs into a cable that connects to the backplane.<br />

The assembly is easily installed <strong>and</strong> removed. You must replace the entire assembly if a fan<br />

fails. If a fan fails, the following events take place:<br />

● An alarm through the power supply is detected as a power alarm.<br />

● The remaining fans go into high speed.<br />

● The red LED on the 650A Global Power supply faceplate lights up.<br />

Specifications<br />

Rack mounting<br />

The G600 Media Gateway can be mounted in a st<strong>and</strong>ard 19-inch (48 centimeter) data rack that<br />

is preinstalled <strong>and</strong> secured according to the EIA 464 or equivalent st<strong>and</strong>ards. The G600 Media<br />

Gateway can be front mounted as shipped or mounted at its midpoint.<br />

The customer must provide the rack, <strong>and</strong> the rack must be installed <strong>and</strong> secured prior to the<br />

G600 Media Gateway installation. The customer must also provide AC power to the rack. The<br />

technicians who install the G600 Media Gateway do not usually have the tools or proper training<br />

<strong>for</strong> data rack installation.<br />

Installation requires 1 foot (30 centimeters) of clearance in the rear, <strong>and</strong> 18 inches (45<br />

centimeters) of clearance in the front, which is consistent with the EIA 310 st<strong>and</strong>ards. In a<br />

2-cabinet configuration, the dimensions of the TDM/LAN cable require that you mount the B<br />

cabinet directly over the A cabinet.<br />