Sneak current protection<br />

Extraneous power induces sneak current protection to protect building wiring with fuses. The<br />

fuses protect wiring between the network interface <strong>and</strong> trunk circuits. The fuses also protect the<br />

circuit packs.<br />

All incoming trunks <strong>and</strong> outgoing trunks <strong>and</strong> off-premises station lines pass through the sneak<br />

fuses. 507B sneak fuse panels are installed on the system side of the network interface.<br />

Sneak current protectors must be either UL-listed or CSA-certified or must comply with local<br />

safety st<strong>and</strong>ards. Sneak current protectors must have a maximum rating of 350 milliamperes<br />

(mA) <strong>and</strong> a minimum voltage rating of 600 volts, or as required by local regulations.<br />

Lightning protection<br />

A coupled bonding conductor (CBC) in the cabinet ground wiring protects the system from<br />

lightning. The CBC runs adjacent to wires in a cable <strong>and</strong> causes mutual coupling between itself<br />

<strong>and</strong> the wires. The mutual coupling reduces the voltage difference between ground <strong>and</strong> the<br />

switch.<br />

Ensure that the CBC connects to a telecommunications cable that is firmly connected to an<br />

approved ground. In multiple-story buildings, you must connect the CBC to an approved ground<br />

at each floor.<br />

The CBC can be any of the following configurations:<br />

● a 10 AWG (5.3 millimeters2/2.6 millimeters) ground wire,<br />

● a continuous cable sheath that surrounds wires within a cable, or<br />

● six unused pairs of wire within a cable that are twisted <strong>and</strong> soldered together.<br />

The CBC connects from the cabinet single-point ground bar in an AC-powered cabinet or the<br />

ground discharge bar in a DC-powered cabinet to the terminal bar at the cross-connect field.<br />

When there is an auxiliary cabinet, a 6 AWG (13.3 millimeters2 /4.1 millimeters) wire connects<br />

the system cabinet single-point ground block to the Auxiliary cabinet ground block. The ground<br />

wire routes as closely as possible to the cables that connect the system cabinet to the Auxiliary<br />

cabinet.<br />

If equipment is not present in the Auxiliary cabinet, you must preserve ground integrity. Plug the<br />

power supply <strong>for</strong> this equipment into one of the two convenience outlets on the rear of the<br />

MCC1. The convenience outlets are fused at 5 A. A dedicated maintenance terminal plugs into<br />

the other convenience outlet.<br />

Earthquake protection<br />

For earthquake or disaster bracing, the cabinets bolt to the floor. Other areas might require<br />

additional bracing. Contact your <strong>Avaya</strong> representative <strong>for</strong> earthquake requirements at the<br />

location of the system installation.<br />

Issue 6 February 2007 419