Cabinet type Height<br />

(inches)<br />

DC power cabinet 3 20 (51 cm) 27 (69 cm) 22 (56 cm) Front <strong>and</strong> rear<br />

38 (97 cm)<br />

Large battery<br />

cabinet<br />

100<br />

200<br />

300<br />

400<br />

27 (69 cm)<br />

42 (107 cm)<br />

42 (107 cm)<br />

57 (145 cm)<br />

Floor load requirements<br />

55 (140 cm)<br />

55 (140 cm)<br />

55 (140 cm)<br />

55 i (140 cm)<br />

21 (53 cm)<br />

21 (53 cm)<br />

21 (53 cm)<br />

21 (53 cm)<br />

1. This row includes the auxiliary cabinet, the global AC cabinet, <strong>and</strong> the global DC cabinet.<br />

2. Cable slack manager is used with MCC1 Media Gateway <strong>and</strong> the SCC1 Media Gateway.<br />

Front <strong>and</strong> rear<br />

38 (97 cm)<br />

3. DC power cabinet requires a floor area of 8 square feet (0.74 square meters). The DC power cabinet also<br />

requires 38 inches (97 cm) between the cabinet <strong>and</strong> the wall.<br />

The equipment room floor must meet the commercial floor loading code of at least 50 pounds<br />

per square foot (242 kilograms per square meter). Floor plans usually allocate space around the<br />

front, the ends, <strong>and</strong>, if necessary, the rear <strong>for</strong> maintenance access of the Media Gateways.<br />

Additional floor support might be required if the floor load is greater than 50 pounds per square<br />

foot (242 kilograms per square meter). The following table contains in<strong>for</strong>mation about weight<br />

<strong>and</strong> floor loading <strong>for</strong> the media gateway <strong>and</strong> battery.<br />

Media<br />

Gateway<br />

Width (inches) Depth (inches) Clearance<br />

(inches)<br />

Weight (pounds) Floor loading (pounds<br />

per square foot)<br />

SCC1 125 (56 kg) 31 (148.9 kg/m 2 )<br />

MCC1 200 to 800 (90 to<br />

363 kg)<br />

Notes<br />

130 (624.2 kg/m 2 ) Includes<br />

auxiliary,<br />

global AC, <strong>and</strong><br />

global DC<br />

cabinets<br />