Appendix A: Specifications <strong>for</strong> DEFINITY media gateways<br />

Figure 86: Battery charger (optional part of J58890CE-2) (front)<br />

The battery charger is used only without an uninterruptible power supply (UPS). The charger<br />

contains:<br />

● Three 48-VDC batteries <strong>for</strong> backup power to the cabinet<br />

● A DC power relay to connect the batteries into the power circuit if a main power failure is<br />

detected<br />

Circuit breaker<br />

The circuit breaker protects the AC input power to the cabinet <strong>and</strong> serves as the main AC input<br />

disconnect switch. The circuit breaker has two poles <strong>for</strong> 120 VAC or three poles <strong>for</strong> 208 VAC or<br />

240 VAC. If a problem develops, the circuit breaker automatically opens <strong>and</strong> removes the AC<br />

power input.<br />

48-VDC batteries<br />

The three series-connected 48-VDC batteries produce a nominal 144 VDC that is fused at 20 A.<br />

The batteries are trickle-charged from the battery charger.<br />

Battery charger<br />

When AC power restores after an outage, the battery charger converts a 120-VAC input to a DC<br />

voltage that recharges the batteries. The batteries usually recharge within 24 hours.<br />

DC power relay<br />

Batteries<br />

The DC power relay disconnects the batteries from a system that is using AC power. The relay<br />

also disconnects the batteries if power fails <strong>for</strong> more than:<br />

● 10 minutes in a st<strong>and</strong>ard-reliability system<br />

● 5 minutes in high reliability <strong>and</strong> critical reliability systems<br />

● 10 minutes in an expansion port network (EPN)<br />

Battery<br />

charger<br />

psdfbatt RPY 053097<br />

406 <strong>Hardware</strong> <strong>Description</strong> <strong>and</strong> <strong>Reference</strong> <strong>for</strong> <strong>Avaya</strong> Communication Manager