Temperature <strong>and</strong> humidity<br />

The G600 Media Gateway must be installed in a well-ventilated area. Maximum equipment<br />

per<strong>for</strong>mance is achieved at an ambient temperature between 40 °F <strong>and</strong> 120 °F (4 °C <strong>and</strong> 49 °C)<br />

<strong>for</strong> a short-term operation of not more then 72 consecutive hours or 15 days in one year. A<br />

continuous operation requires up to 110 °F (43 °C).<br />

The relative humidity range is 10 to 95% at up to 84 °F (29 °C). Above 84 °F (29 °C), maximum<br />

relative humidity decreases from 95% to 32% at 120 °F (49 °C). Installations outside these limits<br />

might reduce system life or affect operation. The recommended temperature range <strong>and</strong><br />

humidity range is 65 °F to 85 °F (18 °C to 29 °C) at 20 to 60% relative humidity.<br />

Power requirements<br />

The G600 Media Gateway has the following AC power requirements using the 650A integrated<br />

power supply.<br />

Note: There<br />

Note:<br />

is no integrated DC power supply. DC rectifiers can be used if desired;<br />

follow manufacturer’s instructions.<br />

Power sources Power input receptacles 1<br />

Single-phase 120-VAC with<br />

neutral<br />

Single-phase 240-VAC with<br />

neutral<br />

120-VAC, 60-Hz NEMA 5-15R 15<br />

240-VAC, 50-Hz IEC 320 10<br />

1. Japan installations use country-specific receptacles <strong>for</strong> 100 VAC <strong>and</strong> 200 VAC,<br />

50/60 Hz.<br />

172 <strong>Hardware</strong> <strong>Description</strong> <strong>and</strong> <strong>Reference</strong> <strong>for</strong> <strong>Avaya</strong> Communication Manager<br />

Circuit<br />

Amperes