04.06.2013 Views

1 2 3 4 A - SIPROTEC

1 2 3 4 A - SIPROTEC

1 2 3 4 A - SIPROTEC

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

2.2 Differential Protection<br />

<strong>SIPROTEC</strong>, 7UT6x, Manual<br />

C53000-G1176-C230-2, Release date 06.2012<br />

Functions<br />

2.2 Differential Protection<br />

The differential protection represents the main protection feature of the device. It is based on current<br />

comparison under consideration of the transformation ratio of the transformer.7UT6x is suitable for unit protection<br />

of transformers, generators, motors, reactors, short lines, also with feeders, and (under observance of the<br />

available number of current inputs) for busbar arrangements. Protection of generator/transformer units, transformer/winding<br />

combinations or transformer/starpoint former, can also be realised. 7UT612 allows up to two,<br />

7UT613 and 7UT633 allow up to 3, 7UT635 allows up to 5 three-phase measuring locations.<br />

7UT6x can be used as a single-phase differential protection relay. In this case, 7UT612 allows up to 7, 7UT613<br />

and 7UT633 allow up to 9, and 7UT635 up to 12 measuring locations, e.g. currents from a busbar with up to 7<br />

or 9 or 12 feeders.<br />

The protected zone is selectively limited by the CTs at its ends.<br />

2.2.1 Functional Description of the Differential Protection<br />

Processing of the measured values depends on the way the differential protection is used. This section<br />

discusses first the differential protection function in general, regardless of the type of protected object. A singlephase<br />

system is referred to. Particulars with regard to the individual protected objects follow thereafter.<br />

Basic Principle with Two Sides<br />

Differential protection is based on current comparison. It makes use of the fact that a protected object carries<br />

always the same current i (dashed line in 2-17 below) at its two sides in healthy operation. This current flows<br />

into one side of the considered zone and leaves it again on the other side. A difference in currents is a clear<br />

indication of a fault within this section. If the actual current transformation ratio is the same, the secondary windings<br />

of the current transformers CT1 and CT2 at the sides of the protected object can be connected to form a<br />

closed electric circuit with a secondary current I; a measuring element M, which is connected to the electrical<br />

balance point, remains at zero current in healthy operation.<br />

Figure 2-17 Basic principle of differential protection for two sides (single-phase illustration)<br />

When a fault occurs in the zone limited by the transformers, a current i 1 + i 2, which is proportional to the fault<br />

currents I 1 + I 2 flowing in from both sides is fed to the measuring element. As a result, the simple circuit shown<br />

in Figure 2-17 ensures a reliable tripping of the protection if the fault current flowing into the protected zone<br />

during a fault is high enough for the measuring element M to respond.<br />

105

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!