No. Information Type of Information<br />

2.19.4 Malfunction Responses of the Device<br />

<strong>SIPROTEC</strong>, 7UT6x, Manual<br />

C53000-G1176-C230-2, Release date 06.2012<br />

Comments<br />

30107 Err. IN CT IX2 OUT Err: inconsist. jumper/setting CT IX2<br />

30108 Err. IN CT IX3 OUT Err: inconsist. jumper/setting CT IX3<br />

30109 Err. IN CT IX4 OUT Err: inconsist. jumper/setting CT IX4<br />

30120 brk. wire IL1M1 OUT Broken wire IL1 measurement location 1<br />

30121 brk. wire IL2M1 OUT Broken wire IL2 measurement location 1<br />

30122 brk. wire IL3M1 OUT Broken wire IL3 measurement location 1<br />

30123 brk. wire IL1M2 OUT Broken wire IL1 measurement location 2<br />

30124 brk. wire IL2M2 OUT Broken wire IL2 measurement location 2<br />

30125 brk. wire IL3M2 OUT Broken wire IL3 measurement location 2<br />

30126 brk. wire IL1M3 OUT Broken wire IL1 measurement location 3<br />

30127 brk. wire IL2M3 OUT Broken wire IL2 measurement location 3<br />

30128 brk. wire IL3M3 OUT Broken wire IL3 measurement location 3<br />

30129 brk. wire IL1M4 OUT Broken wire IL1 measurement location 4<br />

30130 brk. wire IL2M4 OUT Broken wire IL2 measurement location 4<br />

30131 brk. wire IL3M4 OUT Broken wire IL3 measurement location 4<br />

30132 brk. wire IL1M5 OUT Broken wire IL1 measurement location 5<br />

30133 brk. wire IL2M5 OUT Broken wire IL2 measurement location 5<br />

30134 brk. wire IL3M5 OUT Broken wire IL3 measurement location 5<br />

30135 Incons.CBaux M1 OUT Incons. M1: CBaux open/ curr. persistent<br />

30136 Incons.CBaux M2 OUT Incons. M2: CBaux open/ curr. persistent<br />

30137 Incons.CBaux M3 OUT Incons. M3: CBaux open/ curr. persistent<br />

30138 Incons.CBaux M4 OUT Incons. M4: CBaux open/ curr. persistent<br />

30139 Incons.CBaux M5 OUT Incons. M5: CBaux open/ curr. persistent<br />

30140 Incons.CBaux S1 OUT Incons. S1: CBaux open/ curr. persistent<br />

30141 Incons.CBaux S2 OUT Incons. S2: CBaux open/ curr. persistent<br />

30142 Incons.CBaux S3 OUT Incons. S3: CBaux open/ curr. persistent<br />

30143 Incons.CBaux S4 OUT Incons. S4: CBaux open/ curr. persistent<br />

30144 Incons.CBaux S5 OUT Incons. S5: CBaux open/ curr. persistent<br />

30145 Fail.Disconnect OUT Failure: disconnect measurment location<br />

Functions<br />

2.19 Monitoring Functions<br />

Depending on the type of malfunction discovered, an alarm is given, a restart of the processor system is initiated,<br />

or the device is taken out of service. If the fault is still present after three restart attempts the protection<br />

system will take itself out of service and indicate this condition by drop-off of the “Device OK” relay, thus indicating<br />

the device failure. The red LED „ERROR“ on the device front lights up, provided that there is an internal<br />

auxiliary voltage, and the green LED „RUN“ goes off. If the internal auxiliary voltage supply fails, all LEDs are<br />

dark. The following table shows a summary of the most important monitoring functions and the fault reactions<br />

of the device.<br />

307