<strong>SIPROTEC</strong>, 7UT6x, Manual<br />

C53000-G1176-C230-2, Release date 06.2012<br />

Functions<br />

2.1 General<br />

Address 225 ASSIGNM. 4M,4S appears if 4 assigned measuring locations (address 212) have been selected<br />

for 4 sides (address 213). Only one option is possible:<br />

• M1,M2,M3,M4, i.e. the 4 measuring locations are assigned: M1 to side S1, M2 to side S2, M3 to side S3,<br />

M4 to side S4.<br />

Address 226 ASSIGNM. 5M,2S appears if 5 assigned measuring locations (address 212) have been selected<br />

for 2 sides (address 213). The following options are possible:<br />

• M1+M2+M3,M4+M5, i.e. the 5 measuring locations are assigned: M1 and M2 and M3 to side S1, M4 and M5<br />

to side S2.<br />

• M1+M2,M3+M4+M5, i.e. the 5 measuring locations are assigned: M1 and M2 to side S1, M3 and M4 and M5<br />

to side S2.<br />

• M1+M2+M3+M4,M5, i.e. the 5 measuring locations are assigned: M1 and M2 and M3 and M4 to side S1, M5<br />

to side S2.<br />

• M1,M2+M3+M4+M5, i.e. the 5 measuring locations are assigned: M1 to side S1, M2 and M3 and M4 and M5<br />

to side S2.<br />

Address 227 ASSIGNM. 5M,3S appears if 5 assigned measuring locations (address 212) have been selected<br />

for 3 sides (address 213). The following options are possible:<br />

• M1+M2,M3+M4,M5, i.e. the 5 measuring locations are assigned: M1 and M2 to side S1, M3 and M4 to side<br />

S2, M5 to side S3.<br />

• M1+M2,M3,M4+M5, i.e. the 5 measuring locations are assigned: M1 and M2 to side S1, M3 to side S2, M4<br />

and M5 to side S3.<br />

• M1,M2+M3,M4+M5, i.e. the 5 measuring locations are assigned: M1 to side S1, M2 and M3 to side S2, M4<br />

and M5 to side S3.<br />

• M1+M2+M3,M4,M5, i.e. the 5 measuring locations are assigned: M1 and M2 and M3 to side S1, M4 to side<br />

S2, M5 to side S3.<br />

• M1,M2+M3+M4,M5, i.e. the 5 measuring locations are assigned: M1 to side S1, M2 and M3 and M4 to side<br />

S2, M5 to side S3.<br />

• M1,M2,M3+M4+M5, i.e. the 5 measuring locations are assigned: M1 to side S1, M2 to side S2, M3 and M4<br />

and M5 to side S3.<br />

Address 228 ASSIGNM. 5M,4S appears if 5 assigned measuring locations (address 212) have been selected<br />

for 4 sides (address 213). The following options are possible:<br />

• M1+M2,M3,M4,M5, i.e. the 5 measuring locations are assigned: M1 and M2 to side S1, M3 to side S2, M4<br />

to side S3, M5 to side S4.<br />

• M1,M2+M3,M4,M5, i.e. the 5 measuring locations are assigned: M1 to side S1, M2 and M3 to side S2, M4<br />

to side S3, M5 to side S4.<br />

• M1,M2,M3+M4,M5, i.e. the 5 measuring locations are assigned: M1 to side S1, M2 to side S2, M3 and M4<br />

to side S3, M5 to side S4.<br />

• M1,M2,M3,M4+M5, i.e. the 5 measuring locations are assigned: M1 to side S1, M2 to side S2, M3 to side<br />

S3, M4 and M5 to side S4.<br />

Address 229 ASSIGNM. 5M,5S appears if 5 assigned measuring locations (address 212) have been selected<br />

for 5 sides (address 213). Only one option is possible:<br />

• M1,M2,M3,M4,M5, i.e. the 5 measuring locations are assigned: M1 to side S1, M2 to side S2, M3 to side<br />

S3, M4 to side S4, M5 to side S5.<br />