Mounting and Commissioning<br />

3.3 Commissioning<br />

3.3.6 Secondary Tests<br />

422<br />

Checking the individual protection functions of the characteristic curves or pick-up values is not required since<br />

these are part of the firmware programs which are monitored continuously. Analogue inputs are checked at the<br />

primary commissioning at the protective object (Section 3.3 under „Symmetrical Current Tests on the Protective<br />

Object“). Verification of connections, i.e. coupling with the plant, also takes place there. Measured quantities<br />

deviation between the protective functions and phases can be excluded.<br />

Secondary checks can never replace the primary checks described below, as connection errors cannot be<br />

included. They can however be used as theoretical test of the setting values. Should you want to perform a<br />

secondary test, please observe the following hints.<br />

When performing tests with secondary test equipment, attention must be paid that no other measuring values<br />

are applied and that the trip command to the circuit breakers are interrupted.<br />

The tests should be done with the current setting values of the device. If these are not (yet) available, the test<br />

should be done with the preset values.<br />

Note<br />

The measurement accuracy to be achieved depends on the electrical data of the test sources used. The<br />

accuracies specified in the technical specifications can be expected only if the reference conditions in<br />

accordance with VDE 0435/Part 303 or IEC 60255 are adhered to, and precision measurement instruments<br />

are used. The stated tolerances refer to the preset data of the protective object. If the ( reference current transformer<br />

rated current) rated current deviates greatly from the protective object, appropriately high pickup<br />

tolerance has to be used.<br />

Differential Protection<br />

Every side of the differential protection can be checked. This is consistent with the simulation of a single source<br />

error. If a side has several measuring locations, the not in a test involved measured inputs remain at zero<br />

current. Checking the pickup value is performed by slowly increasing the test current.<br />

Caution!<br />

Tests with currents that exceed more than 4 times the rated device current cause an overload of the input<br />

circuits and may only be performed for a short time.<br />

See Technical Data<br />

Afterwards the device has to cool off!<br />