Functions<br />

2.4 Time Overcurrent Protection for Phase and Residual Currents<br />

Inrush Restraint<br />

178<br />

At address 2202 InRushRest. 3I0 of the general settings, the inrush restraint can be enabled (ON) or disabled<br />

(OFF). Especially for transformers and if overcurrent time protection is activated on the earthed supply<br />

side, this inrush restraint is required. Function parameters of the inrush restraint are set in „Inrush“.<br />

The inrush restraint is based on the evaluation of the 2nd harmonic present in the inrush current. The ratio of<br />

2nd harmonics to the fundamental component 2.HARM. 3I0 (address 2241) is set to I 2fN/I fN = 15 % as default<br />

setting. It can be used without being changed. To provide more restraint in exceptional cases, where energising<br />

conditions are particularly unfavourable, a smaller value can be set in the above-mentioned address.<br />

If the current exceeds the value indicated in address 2242 or 2243 I Max InRr. 3I0, no restraint will be<br />

provoked by the 2nd harmonic.<br />

Additional Time Overcurrent Protection Functions for Residual Current<br />

In the aforementioned description, the first overcurrent protection for zero sequence current is described. The<br />

differences in the parameter addresses and message numbers of the first, second and third overcurrent protection<br />

are illustrated in the following table. The positions marked by x are identical.<br />

1st time overcurrent protection for residual<br />

current<br />

2nd time overcurrent protection for residual<br />

current<br />

3rd time overcurrent protection for residual<br />

current<br />

Note<br />

Addresses of the<br />

parameters<br />

Addresses of the<br />

dynamic parameters<br />

Message no.<br />

22xx 23xx 191.xxxx(.01)<br />

34xx 35xx 321.xxxx(.01)<br />

36xx 37xx 323.xxxx(.01)<br />

If the time overcurrent protection is assigned to a side of the main protected object, the current values are set<br />

referred to the rated current of that side II/I NS .<br />

<strong>SIPROTEC</strong>, 7UT6x, Manual<br />

C53000-G1176-C230-2, Release date 06.2012