<strong>SIPROTEC</strong>, 7UT6x, Manual<br />

C53000-G1176-C230-2, Release date 06.2012<br />

Functions<br />

2.2 Differential Protection<br />

Figure 2-31 shows an example of an earth fault on the delta side outside the protected zone if an earthed<br />

starpoint former (zigzag winding) is installed within the protected zone. Here, a zero sequence current occurs<br />

on the right side but not on the left, as above. If the starpoint former were outside the protected zone (i.e. CTs<br />

between power transformer and starpoint former), the zero sequence current would not pass through the<br />

measuring point (CTs) and would not have any harmful effect.<br />

Figure 2-31 Example of an earth fault outside the protected transformer with a neutral earthing reactor<br />

within the protected zone<br />

The disadvantage of elimination of the zero sequence current is that the protection becomes less sensitive<br />

(factor 2 / 3 because the zero sequence current amounts to 1 / 3 in case of an earth fault in the protected area.<br />

Therefore, elimination is suppressed in case the starpoint is not earthed (see figure 2-28), or the starpoint<br />

current can be included (figure 2-29). If, for example, a surge voltage arrester is connected to the starpoint, one<br />

should do without the advantage of that option in order to avoid recognition of a breakdown of the surge voltage<br />

arrester as an internal fault. For this purpose, the starpoint of the respective side must be set to Earthed<br />

(addresses 313 STARPNT SIDE 1, 323 STARPNT SIDE 2, 333 STARPNT SIDE 3, 343 STARPNT SIDE 4,<br />

353 STARPNT SIDE 5).<br />

Use on Auto-Transformers<br />

In order to achieve comparable currents for the differential protection, all currents are referred to the winding<br />

(= side) with the highest apparent power rating. This apparent power is named the rated power of the protected<br />

object bezeichnet. If the highest apparent power rating occurs repeatedly, that side which has the higher rated<br />

current will be selected as the reference side, unlike the other protected objects.<br />

Auto-connected windings in auto-transformers can only be connected Y(N)y0 (figure 2-32). If the starpoint is<br />

earthed, all auto-connected windings connected to the system parts (higher and lower voltage system) are<br />

affected. The zero sequence system of both system parts is coupled because of the common starpoint.<br />

Figure 2-32 Auto-transformer with earthed starpoint<br />

119