Functions<br />

2.1 General<br />

66<br />

The mode of connection CONNECTION S2 (address 324) and the vector group numeral VECTOR GRP S2<br />

(address 325) must match the transformer data of the transformer windings at side 2. The vector group numeral<br />

states the phase displacement of side 2 against the reference winding, side 1. It is defined according to IEC as<br />

the multiple of 30°. If the higher voltage side is the reference (side 1), you may take the data directly from the<br />

vector group designation. For instance, for a transformer Yd5 is CONNECTION S2 = D and VECTOR GRP S2<br />

= 5. Every vector group from 0 to 11 can be set provided it is possible (for instance, Yy, Dd and Dz allow only<br />

even, Yd, Yz and Dy allow only odd numerals). For the auto-connected winding of auto-transformers and for<br />

single-phase transformers, only Y 0 is permissible.<br />

If a reference winding other than the higher voltage one is used, it must be noted that this changes the vector<br />

group numeral: e.g. a Yd5 transformer is regarded from the lower voltage side as Dy7.<br />

Figure 2-11 Change of the transformer vector group if the lower voltage side is the reference side —<br />

example<br />

If the power transformer includes more than 2 windings or assigned sides, similar considerations apply for the<br />

further windings (winding 4 and 5 only with 7UT635). If you have declared the starpoint connections of an autotransformer<br />

bank as a separate side in order to establish a current comparison protection for each of the windings<br />

(refer also to Figure 2-7 and the respective notes under „Auto-Transformer Banks“), no settings will be<br />

presented for this side as they would have no meaning for this application. If in an auto-transformer side S3 or<br />

S4 is a compensation winding, the mode of connection is always assumed to be „D“, and only odd-numbered<br />

vector groups can be selected for these sides.<br />

For the winding assigned to side 3, the following data are relevant:<br />

• Address 331 UN-PRI SIDE 3 the primary rated voltage (consider regulating range),<br />

• Address 332 SN SIDE 3 the primary rated apparent power,<br />

• Address 333 STARPNT SIDE 3 the starpoint treatment,<br />

• Address 334 CONNECTION S3 the winding connection mode,<br />

• Address 335 VECTOR GRP S3 the vector group numeral.<br />

For the winding assigned to side 4, the following data are relevant:<br />

• Address 341 UN-PRI SIDE 4 the primary rated voltage (consider regulating range),<br />

• Address 342 SN SIDE 4 the primary rated apparent power,<br />

• Address 343 STARPNT SIDE 4 the starpoint conditioning,<br />

• Address 344 CONNECTION S4 the winding connection mode,<br />

• Address 345 VECTOR GRP S4 the vector group numeral.<br />

<strong>SIPROTEC</strong>, 7UT6x, Manual<br />

C53000-G1176-C230-2, Release date 06.2012