Functions<br />

2.1 General<br />

Differential Protection<br />

38<br />

• Such current comparison is more sensitive to 1-phase earth faults in one of the transformers than the normal<br />

differential protection. This has a certain importance considering that 1-phase earth faults are the most<br />

probable faults in such banks.<br />

• On the other hand, the compensation winding cannot and must not be included into this protection even if it<br />

is accessible and equipped with current transformers. This application variant is based on the current law in<br />

that all currents flowing into a winding must total to zero.<br />

• If this protection variant is desired, set address 105 to PROT. OBJECT = Autotr. node.<br />

• Equal setting is valid for generators and motors. The setting PROT. OBJECT = Generator/Motor also<br />

applies to series reactors and shunt reactors, if a complete 3-phase set of current transformers is connected<br />

to both sides.<br />

• If the device is used for mini-busbars, select the option PROT. OBJECT = 3ph Busbar. The maximum<br />

number of feeders is determined by the greates possible number of three-phase measuring inputs of the<br />

device. 7UT612 allows up to 2, 7UT613 and 7UT633 allow a maximum number of 3, 7UT635 a maximum<br />

of 5 measuring locations. This setting applies also for short lines which are terminated by sets of current<br />

transformers at each terminal. „Short“ means in this context that the current transformer connections from<br />

the CTs to the device do not cause impermissible load to the current transformers.<br />

• The device can be used as single-phase differential protection for busbars, either using one device per<br />

phase or one device connected via external summation CTs. Select the optionPROT. OBJECT = 1ph<br />

Busbar in this case. The maximum number of feeders is determined by the maximum possible number of<br />

single-phase measuring locations of the device (7UT612 provides up to 7, 7UT613 and 7UT633 provide up<br />

to 9, 7UT635 up to 12 measuring locations).<br />

The differential protection is the main protective function of the device. Address 112 DIFF. PROT. is thus set<br />

to Enabled.<br />

Restricted Earth Fault Protection<br />

The Restricted earth fault protection (address 113 REF PROT.) compares the sum of the phase<br />

currents flowing into the three-phase protected object together with the current flowing into the earthed starpoint.<br />

Further information is given in section 2.3.<br />

Note that this is not applicable to the protected object busbar (address 105 PROT. OBJECT= 1ph Busbar<br />

and address 105 PROT. OBJECT= 3ph Busbar).<br />

Restricted Earth Fault Protection 2<br />

The same is true in 7UT613/63x for the second potential restricted earth fault protection at address114 REF<br />

PROT. 2<br />

Dynamic Pickup Switching for Overcurrent Protection<br />

The dynamic parameter switching (address 117 COLDLOAD PICKUP) permits temporary switching to alternative<br />

pickup values in case of overcurrent protection function for phase currents, zero sequence currents and<br />

earth currents. Further information is given in section 2.6.<br />

<strong>SIPROTEC</strong>, 7UT6x, Manual<br />

C53000-G1176-C230-2, Release date 06.2012