Mounting and Commissioning<br />

3.3 Commissioning<br />

448<br />

• In a first step, check whether power measurement is carried out at the desired measuring location, i.e. that<br />

the assignment of the 3-phase voltage transformer set is made correct. The powers are always calculated<br />

from the connected voltages and the currents of that measuring location to which the voltages are assigned.<br />

If the voltage inputs are assigned to a side of the protected object with more than one measuring location,<br />

the sum of the currents flowing into the protected object is decisive.<br />

Address is relevant 261 VT SET. Refer to Subsection 2.1.4 under margin heading „Assignment of Voltage<br />

Measuring Inputs“.<br />

• With closed circuit breaker, the power values can be viewed as primary and secondary measured values in<br />

the front display panel or via the operator or service interface with a personal computer.<br />

Here, again, the „Web-monitor“ is a comfortable help as the vector diagrams also show the correlation<br />

between the currents and voltages. Cyclically and acyclically swapped phases can easily be detected<br />

(see figure ).<br />

• With the aid of the measured power values you are able to verify that they correlate to the load direction,<br />

reading either at the device itself or in DIGSI<br />

P positive, if active power flows into the protected object,<br />

P negative, if active power leaves the protected object,<br />

Q positive, if (inductive) reactive power flows into the protected object,<br />

Q negative, if (inductive) reactive power leaves the protected object.<br />

Figure 3-47 Apparent power<br />

If all signs are inverted this may be intentional. Check in the setting of address 1107 P,Q sign in the power<br />

system data 2 whether the polarity is inverted (see also Subsection 2.1.6.1 under „Sign of Power“). In that case<br />

the signs for active and reactive power are inverse as well.<br />

Otherwise, swapped polarities of the voltage connections may be the cause. If wrong sign is indicated in spite<br />

of correct VT connections, all CT polarities must be wrong!<br />

If the voltage inputs are assigned to a side with more than one current measuring location, currents may flow<br />

through the measuring locations without entering the protective object because they cancel each other out.<br />

Power measurement is not possible in this case. Make sure that the currents for power measurement flow really<br />

through the protected object. Preferably use only one measuring location for the power test.<br />

Finally, disconnect the power plant.<br />