Manual Close Indication of a Circuit Breaker<br />

<strong>SIPROTEC</strong>, 7UT6x, Manual<br />

C53000-G1176-C230-2, Release date 06.2012<br />

Functions<br />

2.1 General<br />

If a protection function is to make use of an external manual-close command indicated via a binary input, you<br />

must have selected that logical input indication during the configuration of the binary inputs that corresponds<br />

to the side or measuring location to which the protection function is assigned. From the internal control, the<br />

device uses the same switching objects that were selected at the addresses 831 to 840.<br />

Example:<br />

Command Duration<br />

If you have assigned the time overcurrent protection for phase currents to measuring location M4 and want it<br />

to receive the manual-close command from circuit breaker CB2, you connect the Close command for breaker<br />

CB2 to a binary input and allocate that input to „>ManualClose M4“ (No 30354).<br />

The minimum trip command duration 851 is set in address TMin TRIP CMD. This duration is valid for all<br />

protection functions which can issue a trip command. This parameter can only be altered in DIGSI at Display<br />

Additional Settings.<br />

2.1.4.5 Settings<br />

Addresses which have an appended "A" can only be changed with DIGSI, under Additional Settings.<br />

Addr. Parameter Setting Options Default Setting Comments<br />

211 No Conn.MeasLoc 2<br />

3<br />

4<br />

5<br />

212 No AssigMeasLoc 2<br />

3<br />

4<br />

5<br />

213 NUMBER OF SIDES 2<br />

3<br />

4<br />

5<br />

216 NUMBER OF ENDS 3<br />

4<br />

5<br />

6<br />

7<br />

8<br />

9<br />

10<br />

11<br />

12<br />

3 Number of connected Measuring<br />

Locations<br />

3 Number of assigned Measuring<br />

Locations<br />

3 Number of Sides<br />

6 Number of Ends for 1 Phase<br />

Busbar<br />

220 ASSIGNM. 2M,2S M1,M2 M1,M2 Assignment at 2 assig.Meas.Loc./<br />

2 Sides<br />

221 ASSIGNM. 3M,2S M1+M2,M3<br />

M1,M2+M3<br />

M1+M2,M3 Assignment at 3 assig.Meas.Loc./<br />

2 Sides<br />

222 ASSIGNM. 3M,3S M1,M2,M3 M1,M2,M3 Assignment at 3 assig.Meas.Loc./<br />

3 Sides<br />

83