Mounting and Commissioning<br />

3.3 Commissioning<br />

452<br />

Figure 3-49 Triggering oscillographic recording with DIGSI — example<br />

Oscillographic recording is immediately started. During the recording, an annunciation is output in the left area<br />

of the status line. Bar segments additionally indicate the progress of the procedure.<br />

The SIGRA or the Comtrade Viewer program is required to view and analyse the oscillographic data.<br />

Such test records are especially informative on power transformers when they are triggered by the switch-on<br />

command of the transformer. Since the inrush current may have the same effect as a single-ended infeed, but<br />

which may not initiate tripping, the effectiveness of the inrush restraint is checked by energising the power<br />

transformer several times.<br />

The trip circuit should be interrupted or the differential protection should be switched to DIFF. PROT. = Block<br />

relay (address 1201) during these tests in order to avoid tripping.<br />

Conclusions as to the effectiveness of the inrush restraint can be drawn from the recording of the differential<br />

currents and the harmonic contents. If necessary the inrush current restraint effect can be increased (= smaller<br />

value of the 2nd harmonic in address 1271 2. HARMONIC) when trip occurs or when the recorded data show<br />

that the second harmonic content does not safely exceed the restraining threshold (address 1271). A further<br />

method to increase inrush restraint is to set the crossblock function effective or to increase the duration of the<br />

crossblock function (address 1272 CROSSB. 2. HARM) (For further details refer to the setting information for<br />

differential protection under „Harmonic Restraint“).<br />

Note<br />

Do not forget to switch on the differential protection (address 1201) after completion of the test.<br />

<strong>SIPROTEC</strong>, 7UT6x, Manual<br />

C53000-G1176-C230-2, Release date 06.2012