04.06.2013 Views

1 2 3 4 A - SIPROTEC

1 2 3 4 A - SIPROTEC

1 2 3 4 A - SIPROTEC

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

Mounting and Commissioning<br />

3.3 Commissioning<br />

418<br />

Message No Meaning see<br />

„par too low:“ 30067 Parameter setting value too small for the indicated address<br />

number<br />

„par too high:“ 30068 Parameter setting value too high for the indicated address<br />

number<br />

„settingFault:“ 30069 Parameter setting implausible for the indicated address number<br />

„Diff Adap.fact.“ 5620 The matching factor of the current transformers for the<br />

differential protection is too great or too small<br />

„Diff err. Set.“ 5623 Differential protection setting not plausible 2.2<br />

REF not avail. 5835 Restricted earth fault protection is not available for the<br />

configured protected object<br />

REF Adap.fact. 5836 The matching factor of the current transformers for restricted<br />

earth fault protection is too great or too small.<br />

REF Err CTstar 5830 There is no single-phase measuring input assigned to the<br />

starpoint current for restricted earth fault protection<br />

2.1.4<br />

2.2<br />

2.1.4<br />

2.1.4<br />

2.3<br />

2.1.4<br />

2.2<br />

„REF err. Set.“ 199.2493 Earth fault differential protection setting not plausible 2.1.1<br />

„REF2 Not avail.“ 205.2491 Restricted earth fault protection 2 is not available for the<br />

configured protected object<br />

„REF2 Adap.fact.“ 205.2494 The matching factor of the current transformers for restricted<br />

earth fault protection 2 is too great or too small.<br />

„REF2 Err CTstar“ 205.2492 There is no single-phase measuring input assigned to the<br />

starpoint current for restricted earth fault protection 2<br />

2.4.1<br />

2.4.1<br />

2.3<br />

2.4.1<br />

2.2<br />

„REF2 err. Set.“ 205.2493 Earth fault differential protection setting not plausible 2.1.1<br />

O/C Ph. not active 1860 Time overcurrent protection for phase currents is not available<br />

for the configured protected object<br />

„O/C Para error“ 023.2493 Settings for time overcurrent protection for phase currents not<br />

plausible<br />

„O/C Ph2 Not av.“ 207.2491 Time overcurrent protection for phase currents 2 is not available<br />

for the configured protected object<br />

„O/C Ph2 err Set“ 207.2493 Settings for time overcurrent protection for phase currents 2 not<br />

plausible<br />

„O/C Ph3 Not av.“ 209.2491 Time overcurrent protection for phase currents 3 is not available<br />

for the configured protected object<br />

„O/C Ph3 err Set“ 209.2493 Settings for time overcurrent protection for phase currents 3 not<br />

plausible<br />

O/C 3I0 not av. 1861 Time overcurrent protection for zero current is not available for<br />

the configured protected object<br />

„O/C 3I0 error“ 191.2493 Settings for time overcurrent protection for zero sequence<br />

current not plausible<br />

„O/C 3I0-2 n/a“ 321.2491 Time overcurrent protection for zero sequence current 2 is not<br />

available for the configured protected object<br />

„O/C3I0-2 errSet“ 321.2493 Settings for time overcurrent protection 2 for zero sequence<br />

current not plausible<br />

„O/C 3I0-3 n/a“ 323.2491 Time overcurrent protection for zero sequence current 3 is not<br />

available for the configured protected object<br />

„O/C3I0-3 errSet“ 323.2493 Settings for time overcurrent protection 3 for zero sequence<br />

current not plausible<br />

O/C 3I0 Err CT 1862 No assignment possible for time overcurrent protection for earth<br />

current<br />

„O/C E error“ 024.2493 Settings for time overcurrent protection for earth current not<br />

plausible<br />

2.1.4<br />

2.4.2<br />

2.1.42.1.6<br />

2.4.2<br />

2.1.42.1.6<br />

2.4.2<br />

2.1.4<br />

2.4.2<br />

2.1.42.1.6<br />

2.4.2<br />

2.1.42.1.6<br />

2.4.2<br />

2.1.4<br />

2.5<br />

Section<br />

<strong>SIPROTEC</strong>, 7UT6x, Manual<br />

C53000-G1176-C230-2, Release date 06.2012