Functions<br />

2.19 Monitoring Functions<br />

2.19.1.3 Monitoring of Measured Quantities<br />

Current Symmetry<br />

290<br />

The device detects and signals most of the interruptions, short-circuits, or wrong connections in the secondary<br />

circuits of current or voltage transformers (an important commissioning aid!). The measured quantities are<br />

periodically checked in the background for this purpose, as long as no system fault is present.<br />

In a healthy three-phase system, a certain ssymmetry of the currents is assumed. The monitoring of the<br />

measured values in the device checks this balance for each 3-phase measuring location. For this, the lowest<br />

phase current is set in relation to the highest. An unbalance is detected, e.g. for measuring location 1, when<br />

|I min|/|I max| < BAL. FACT. I M1 as long as I max/I N > BAL. I LIMIT M1/I N.<br />

I max is the highest of the three phase currents and I min the lowest. The symmetry factor BAL. FACT. I M1<br />

represents the allowable asymmetry of the phase currents while the limit value BAL. I LIMIT M1 is the lower<br />

limit of the operating range of this monitoring (see Figure Current Symmetry Monitoring). Both parameters can<br />

be set. The dropout ratio is about 95%.<br />

Current balance monitoring is available separately for each 3-phase measuring location. For single-phase<br />

differential busbar protection this function would not be of any use and is thus disabled. Unsymmetrical<br />

condition is indicated for the corresponding measuring location e.g. with the alarm „Fail balan. IM1“ (No<br />

30110). At the same time, the common annunciation appears: „Fail I balance“ (No 163).<br />

Figure 2-115 Current symmetry monitoring<br />

<strong>SIPROTEC</strong>, 7UT6x, Manual<br />

C53000-G1176-C230-2, Release date 06.2012