Time Overcurrent Protection for Phase Currents and Residual Current<br />

<strong>SIPROTEC</strong>, 7UT6x, Manual<br />

C53000-G1176-C230-2, Release date 06.2012<br />

Introduction<br />

1.3 Characteristics<br />

• Two definite time delayed overcurrent stages for each of the phase currents and the residual (threefold zero<br />

sequence) current, can be assigned to any of the sides of the protected object or to any measuring point<br />

• Additionally, one inverse time delayed overcurrent stage for each of the phase currents and the residual<br />

current<br />

• Selection of various inverse time characteristics of different standards is possible, alternatively a user<br />

defined characteristic can be specified<br />

• The stages can be combined as desired, different characteristics can be selected for phase currents on the<br />

one hand and the residual current on the other<br />

• External blocking facility for any stage (e.g. for reverse interlocking)<br />

• Instantaneous tripping possible at any stage when closing onto a short-circuit<br />

• Inrush restraint using the second harmonic of the measured current<br />

• Dynamic switchover of the time overcurrent protection settings, e.g. during cold-load start-up of the power<br />

plant<br />

• 3 time overcurrent protection functions each for phase currents and zero sequence current possible (only<br />

7UT613/63x)<br />

Time Overcurrent Protection for Earth Current<br />

• Two definite time delayed overcurrent stages for the earth current, e.g. current between starpoint and earth<br />

• Additionally, one inverse time delayed overcurrent stage for the earth current<br />

• Selection of various inverse time characteristics of different standards is possible, alternatively a user<br />

defined characteristic can be specified<br />

• The three can be combined as desired<br />

• External blocking facility for any desired stage (e.g. for reverse interlocking)<br />

• Instantaneous trip when switching on a dead fault with any desired stage<br />

• Inrush restraint function with 2nd harmonic<br />

• Dynamic switchover of the time overcurrent parameters, e.g. during cold-loaded start-up of the power plant<br />

• 2 time overcurrent protection functions for earth current possible (only 7UT613/63x)<br />

1-phase Overcurrent Protection<br />

• Two definite time delayed overcurrent stages which can be combined as desired<br />

• For any 1-phase overcurrent detection<br />

• Can be assigned to the „normal “1-phase current input or to the highly sensitive current input<br />

• Suitable for detection of very small current (e.g. for high-impedance unit protection or tank leakage<br />

protection)<br />

• Suitable for detection of any desired AC voltage using an external series resistor (e.g. for high-impedance<br />

unit protection)<br />

• External blocking facility for any stage<br />

25