04.06.2013 Views

1 2 3 4 A - SIPROTEC

1 2 3 4 A - SIPROTEC

1 2 3 4 A - SIPROTEC

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

Functions<br />

2.9 Thermal Overload Protection<br />

Output of Results<br />

232<br />

The hot-spot temperature is calculated for the winding which corresponds to the side of the protected object<br />

configured for overload protection (Subsection 2.1.4, margin heading „Further 3-phase Protection Functions“,<br />

address 442). The calculation includes the current of that side and the cooling temperature measured at a<br />

certain measuring point. The phase information is taken from the concerned phase in case of generators,<br />

motors, etc., or wye- or zigzag-connected transformer windings; in case of delta-connected transformer<br />

windings the phase-difference currents are decisive which correspond to the current flowing in the winding.<br />

There are two thresholds which can be set. They output a warning (Stage 1) and an alarm (Stage 2) signal.<br />

When the alarm signal is assigned to a trip output, it can also be used for tripping the circuit breaker(s).<br />

For the middle ageing rate, there is also a threshold for each of the warning and the alarm signal.<br />

The status can be read out from the operational measured values at any time. The information includes:<br />

• hot-spot temperature for each winding in °C or °F (as configured),<br />

• relative ageing rate expressed in per unit,<br />

• load backup up to warning signal (Stage 1) expressed in per cent,<br />

• load backup up to alarm signal (Stage 2) expressed in per cent.<br />

Further limit values can be set on the thermobox itself, as in Section „RTD-Boxes for Overload Recognition“<br />

2.9.5 Setting Notes<br />

General<br />

Note<br />

The first thermal overload protection is described in the setting instructions. The parameter addresses and<br />

message numbers of the second thermal overload protection are described at the end of the setting instructions<br />

under „Additional Thermal Overload Protection Functions“.<br />

The overload protection can be assigned to any desired side of the protected object. Since the cause of the<br />

overload current is outside the protected object, the overload current is a through-flowing current, the overload<br />

protection may be assigned to a feeding or a non-feeding side. When setting the assignment of the protection<br />

functions to the sides of the protected object according to Subsection 2.1.4, margin heading „Further 3-Phase<br />

Protection functions“, you have performed this assignment under address 442 THERM. O/L AT. Respective<br />

notes are given here.<br />

Three methods are available for overload detection, as set out above. During configuration of the functional<br />

scope (section 2.1.3.1) it was set under address 142 THERM. OVERLOAD whether the overload protection must<br />

function according to the thermal replica (THERM. OVERLOAD = th rep w.o. sen), if necessary, under<br />

inclusion of the environmental or coolant temperature (THERM. OVERLOAD = th repl w. sens) or whether<br />

the hot-spot calculation according to IEC 60354 must be executed (THERM. OVERLOAD = IEC354). In the<br />

latter two cases, at least one RTD-box 7XV5662-xAD must be connected to the device in order to digitally<br />

inform the device about the coolant temperature. The required data for the RTD-box were set under address<br />

191 RTD CONNECTION (section 2.1.3.1).<br />

Under address 4201 THERM. OVERLOAD overload protection ON or OFF can be set. If address 142 THERM.<br />

OVERLOAD has been set to th rep w.o. sen during configuration of the functional scope, the setting Alarm<br />

Only is also possible. With that latter setting the protection function is active but only outputs an alarm when<br />

the tripping temperature rise is reached, i.e. the output function is not active. The option Block relay allows<br />

to operate the protection but the trip output relay is blocked.<br />

<strong>SIPROTEC</strong>, 7UT6x, Manual<br />

C53000-G1176-C230-2, Release date 06.2012

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!