04.06.2013 Views

1 2 3 4 A - SIPROTEC

1 2 3 4 A - SIPROTEC

1 2 3 4 A - SIPROTEC

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

<strong>SIPROTEC</strong>, 7UT6x, Manual<br />

C53000-G1176-C230-2, Release date 06.2012<br />

Functions<br />

2.1 General<br />

When using the circuit breaker failure protection (section 2.17) (address 470 BREAKER FAIL.AT) please<br />

make sure that the assignment of this protection function corresponds to that side or measuring location whose<br />

current actually flows through the circuit breaker to be monitored. In the example shown in Figure 2-2, the<br />

assignment must be set in address BREAKER FAIL.AT to Side 1 if you want to monitor the circuit breaker<br />

of the high-voltage side, since both currents flow through the breaker (via M1 and M2). If on the other hand you<br />

want to monitor the circuit breaker of the cable feeder, you set address BREAKER FAIL.AT to Measuring<br />

loc.5. When assigning the circuit breaker failure protection function, make sure that the breaker auxiliary<br />

contacts or feedback information are correctly configured and assigned.<br />

If you do not wish to assign any measuring location or side to the circuit breaker failure protection because you<br />

want only the breaker position to be processed, set BREAKER FAIL.AT to Ext. switchg. 1. In this case,<br />

the protection handles only the breaker position but not any current flow for its operation. This allows even to<br />

monitor a circuit breaker the current of which is not connected to the device. But you have to ensure that the<br />

feedback information of this breaker is correctly connected and configured.<br />

In 7UT613/63x, you can monitor another m.c.b. using the second circuit breaker failure protection. The<br />

considerations for the assignment in address 471 BREAKER FAIL2AT correspond to those for the first circuit<br />

breaker failure protection.<br />

Further 1-phase Protection Functions<br />

The 1-phase protection functions evaluate the 1-phase measuring current of 1-phase additional measuring<br />

input. It is irrelevant in this context whether the connect current belongs to the main protected object or not.<br />

Only the current connected to the additional measuring input is decisive.<br />

The device must now be informed which current is to be evaluated by the 1-phase protection functions.<br />

Address 424 DMT/IDMT E AT assigns the time overcurrent protection for earth current (section 2.5) to a<br />

1-phase additional measuring input. In most cases this will be the current flowing in the neutral leads of an<br />

earthed winding, measured between the starpoint and the earth electrode. In figure 2-2 the auxiliary measuring<br />

location X3 would be a good choice; so you set here AuxiliaryCT IX3. As this protection function is<br />

autonomous, i.e. independent of any other protection function, any 1-phase additional measuring input can be<br />

used. This requires, however, that it is not a high-sensitivity measuring input and, of course, that it is connected.<br />

Please note also that the earth overcurrent protection will receive from the auxiliary measuring location<br />

assigned here not only its measured value, but also circuit breaker information (current flow and manual-close<br />

detection).<br />

The second earth overcurrent protection can be assigned to another single-phase measuring location<br />

according to the same aspects under address 438 DMT/IDMT E2 AT.<br />

Address 427 DMT 1PHASE AT assigns the single-phase time overcurrent protection (section 2.7). This<br />

protection function is mainly used for high-sensitivity current measurement, e.g. for tank leakage protection or<br />

high-impedance differential protection. Therefore a high-sensitivity 1-phase additional measuring input is<br />

particularly suited for it. In figure 2-2 this would be the auxiliary measuring location X4; so you set this address<br />

to AuxiliaryCT IX4. However, it is also possible to assign this protection function to any other additional<br />

measuring input used, regardless of its sensitivity.<br />

81

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!