Addr. Parameter Function C Setting Options Default Setting Comments<br />

361 UN GEN/MOTOR P.System Data 1 0.4 .. 800.0 kV 21.0 kV Rated Primary Voltage<br />

Generator/Motor<br />

<strong>SIPROTEC</strong>, 7UT6x, Manual<br />

C53000-G1176-C230-2, Release date 06.2012<br />

Appendix<br />

A.8 Settings<br />

362 SN GEN/MOTOR P.System Data 1 0.20 .. 5000.00 MVA 70.00 MVA Rated Apparent Power of the<br />

Generator<br />

370 UN BUSBAR P.System Data 1 0.4 .. 800.0 kV 110.0 kV Rated Primary Voltage Busbar<br />

371 I PRIMARY OP. P.System Data 1 1 .. 100000 A 200 A Primary Operating Current of<br />

Busbar<br />

372 I PRIMARY OP S1 P.System Data 1 1 .. 100000 A 200 A Primary Operating Current<br />

Side 1<br />

373 I PRIMARY OP S2 P.System Data 1 1 .. 100000 A 200 A Primary Operating Current<br />

Side 2<br />

374 I PRIMARY OP S3 P.System Data 1 1 .. 100000 A 200 A Primary Operating Current<br />

Side 3<br />

375 I PRIMARY OP S4 P.System Data 1 1 .. 100000 A 200 A Primary Operating Current<br />

Side 4<br />

376 I PRIMARY OP S5 P.System Data 1 1 .. 100000 A 200 A Primary Operating Current<br />

Side 5<br />

381 I PRIMARY OP 1 P.System Data 1 1 .. 100000 A 200 A Primary Operating Current End 1<br />

382 I PRIMARY OP 2 P.System Data 1 1 .. 100000 A 200 A Primary Operating Current End 2<br />

383 I PRIMARY OP 3 P.System Data 1 1 .. 100000 A 200 A Primary Operating Current End 3<br />

384 I PRIMARY OP 4 P.System Data 1 1 .. 100000 A 200 A Primary Operating Current End 4<br />

385 I PRIMARY OP 5 P.System Data 1 1 .. 100000 A 200 A Primary Operating Current End 5<br />

386 I PRIMARY OP 6 P.System Data 1 1 .. 100000 A 200 A Primary Operating Current End 6<br />

387 I PRIMARY OP 7 P.System Data 1 1 .. 100000 A 200 A Primary Operating Current End 7<br />

388 I PRIMARY OP 8 P.System Data 1 1 .. 100000 A 200 A Primary Operating Current End 8<br />

389 I PRIMARY OP 9 P.System Data 1 1 .. 100000 A 200 A Primary Operating Current End 9<br />

390 I PRIMARY OP 10 P.System Data 1 1 .. 100000 A 200 A Primary Operating Current<br />

End 10<br />

391 I PRIMARY OP 11 P.System Data 1 1 .. 100000 A 200 A Primary Operating Current<br />

End 11<br />

392 I PRIMARY OP 12 P.System Data 1 1 .. 100000 A 200 A Primary Operating Current<br />

End 12<br />

396 PHASE SELECTION P.System Data 1 Phase 1<br />

Phase 2<br />

Phase 3<br />

Phase 1 Phase selection<br />

403 I PRIMARY OP M3 P.System Data 1 1 .. 100000 A 200 A Primary Operating Current Meas.<br />

Loc. 3<br />

404 I PRIMARY OP M4 P.System Data 1 1 .. 100000 A 200 A Primary Operating Current Meas.<br />

Loc. 4<br />

405 I PRIMARY OP M5 P.System Data 1 1 .. 100000 A 200 A Primary Operating Current Meas.<br />

Loc. 5<br />

408 UN-PRI M3 P.System Data 1 0.4 .. 800.0 kV 110.0 kV Rated Primary Voltage<br />

Measuring Loc. 3<br />

409 UN-PRI U4 P.System Data 1 0.4 .. 800.0 kV 110.0 kV Rated Primary Voltage U4<br />

413 REF PROT. AT P.System Data 1 Side 1<br />

Side 2<br />

Side 3<br />

Side 4<br />

Side 5<br />

auto-connected<br />

n.assigMeasLoc3<br />

n.assigMeasLoc4<br />

n.assigMeasLoc5<br />

414 REF PROT. 2 AT P.System Data 1 Side 1<br />

Side 2<br />

Side 3<br />

Side 4<br />

Side 5<br />

auto-connected<br />

n.assigMeasLoc3<br />

n.assigMeasLoc4<br />

n.assigMeasLoc5<br />

Side 1 Restricted earth fault prot.<br />

assigned to<br />

Side 1 Restricted earth fault prot2<br />

assigned to<br />

605