04.06.2013 Views

1 2 3 4 A - SIPROTEC

1 2 3 4 A - SIPROTEC

1 2 3 4 A - SIPROTEC

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

Functions<br />

2.4 Time Overcurrent Protection for Phase and Residual Currents<br />

2.4.2.1 Setting Notes<br />

General<br />

164<br />

Note<br />

The first overcurrent protection for phase currents is described in the setting instructions. The parameter<br />

addresses and message numbers of the second and third overcurrent protection are described at the end of<br />

the setting instructions under „Additional Overcurrent Protection Functions for Phase Currents“.<br />

During configuration of the functional scope (section 2.1.3) the characteristic type is determined under address<br />

120 DMT/IDMT Phase. Only the settings for the selected characteristic can be performed here. The definite<br />

time stages I>> and I> are available in all cases.<br />

If a second or third phase overcurrent protection is used, this must be configured accordingly in address 130<br />

DMT/IDMT Phase2 and 132 DMT/IDMT Phase3.<br />

Each protection function must be assigned to a side of the main protected object or another 3-phase current<br />

measuring location. This can be carried out separately for each protection function (section 2.1.4 under margin<br />

heading „Additional Three-phase Protection Functions“). Consider also the assignment of the measured<br />

current inputs of the device against the measuring locations (current transformer sets) of the power plant<br />

(section 2.1.4 under margin heading „Assignment of 3-phase Measuring Locations“).<br />

Note<br />

If the time overcurrent protection is assigned to a side of the main protected object, the current values are set<br />

referred to the rated current of that side II/I NS. In other cases, current values are set in amps.<br />

At address 2001 PHASE O/C, phase overcurrent protection may be switched to ON or OFF. The option Block<br />

relay allows to operate the protection but the trip output relay is blocked.<br />

Address 2008 MANUAL CLOSE determines which phase current stage is to be activated instantaneously with<br />

a detected manual close. Settings I>> instant. and I> instant. can be set independently from the selected<br />

type characteristics;Ip instant. is only available if one of the inverse time stages is configured. This<br />

setting can only be made with DIGSI under Additional Settings.<br />

If time overcurrent protection is applied on the feeding side of a transformer, select the higher stage<br />

I>>, which does not pick up by the inrush current or set the manual close feature to Inactive.<br />

In address 2002 InRushRest. Ph inrush restraint (restraint with 2nd harmonic) is enabled or disabled for all<br />

phase current stages of time overcurrent protection (except stage I>>). Set ON if one time overcurrent protection<br />

stage is to operate at the supply side of a transformer. Otherwise, retain setting OFF. If you intend to set a<br />

very small pickup value for any reason, consider that the inrush restraint function cannot operate below 10 %<br />

nominal current (lower limit of harmonic filtering).<br />

<strong>SIPROTEC</strong>, 7UT6x, Manual<br />

C53000-G1176-C230-2, Release date 06.2012

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!