An update is made:<br />

Exiting the Procedure<br />

<strong>SIPROTEC</strong>, 7UT6x, Manual<br />

C53000-G1176-C230-2, Release date 06.2012<br />

Mounting and Commissioning<br />

3.3 Commissioning<br />

• For the particular hardware component, if a command for change to another state was successful,<br />

• For all hardware components if the Update button is clicked,<br />

• For all hardware components with cyclical updating (cycle time is 20 sec) if the Automatic Update (20 sec)<br />

field is marked.<br />

To end the hardware test, click on Close. The dialog box closes. Thus, all the hardware components are set<br />

back to the operating state specified by the plant states. The processor system is restarted, then the device is<br />

ready for operation.<br />

3.3.5 Checking the Setting Consistency<br />

The 7UT6x device checks the settings of the protection functions against the corresponding configuration parameters.<br />

Any inconsistencies will be reported. For instance, earth fault differential protection cannot be applied<br />

if there is no measuring input for the starpoint current between starpoint of the protected object and the earthing<br />

electrode.<br />

In the operational or spontaneous annunciations also check if there are any fault annunciations from the device.<br />

The device also checks the matching factors between the rated currents of the CT’s and the operational<br />

currents of the protected object(s) as processed by the protection functions. If very high deviations combined<br />

with sensitive protection settings are discovered an alarm is output which also indicates the suspicious setting<br />

address(es).<br />

Table 3-29 Indications on inconsistencies<br />

Message No Meaning see<br />

„Error1A/5Awrong“ 192 Setting of the rated secondary currents on input/output board<br />

inconsistent, general<br />

„Err. IN CT M1“<br />

to<br />

„Err. IN CT M5“<br />

„Err.IN CT1..3“<br />

to<br />

„Err.IN CT10..12“<br />

„Err. IN CT IX1“<br />

to<br />

„Err. IN CT IX4“<br />

30097<br />

to<br />

30101<br />

30102<br />

to<br />

30105<br />

30106<br />

to<br />

30109<br />

Setting of the rated secondary currents inconsistent for the<br />

indicated measured current input (3-phase inputs)<br />

Setting of the rated secondary currents inconsistent for the<br />

indicated measured current input (inputs for single-phase busbar<br />

protection)<br />

Setting of the rated secondary currents inconsistent for the<br />

indicated measured current input (single-phase inputs)<br />

„FaultConfig/Set“ 311 Group indication for configuration error<br />

„GenErrGroupConn<br />

“<br />

312 General: Error in transformer connection group 2.1.4<br />

„GenErrEarthCT“ 313 Error in single-phase inputs for earth fault differential protection 2.1.4<br />

„GenErrSidesMeas“ 314 Error in assignment of sides and/or measuring locations 2.1.4<br />

Section<br />

2.1.4<br />

3.1.2 („Switch<br />

elements on printed<br />

circuit boards“)<br />

2.1.4<br />

3.1.2 („Switch<br />

elements on printed<br />

circuit boards“)<br />

2.1.4<br />

3.1.2 („Switch elements<br />

on printed circuit<br />

boards“)<br />

2.1.4<br />

3.1.2 („Switch<br />

elements on printed<br />

circuit boards“)<br />

417