Mounting and Commissioning<br />

3.3 Commissioning<br />

Exiting the Test Mode<br />

414<br />

To end the System Interface Test, click on Close. The dialog box closes. The processor system is restarted,<br />

then the device is ready for operation.<br />

Test in Command Direction<br />

Data which are normally linked via binary inputs (first character „>“) are likewise checked with this procedure.<br />

The information transmitted in command direction must be indicated by the central station. Check whether the<br />

reaction is correct.<br />

3.3.4 Checking the switching states of the binary Inputs/Outputs<br />

Prefacing Remarks<br />

The binary inputs, outputs, and LEDs of a <strong>SIPROTEC</strong> 4 device can be individually and precisely controlled in<br />

DIGSI. This feature is used to verify control wiring from the device to plant equipment (operational checks)<br />

during commissioning. This test option should however definitely „not“ be used while the device is in service<br />

on a live system.<br />

DANGER!<br />

A changing of switching states by means of the test function causes a real change of the operating<br />

state at the <strong>SIPROTEC</strong> 4 device. Connected operating equipment such as circuit breakers or<br />

disconnectors will be switched in this way!<br />

Non-observance of the following measure will result in death, severe personal injury or substantial property<br />

damage.<br />

Equipment used to allow switching such as circuit breakers or disconnectors is to be checked only during commissioning.<br />

Do not under any circumstances check them by means of the testing mode during „real“ operation<br />

performing transmission and reception of messages via the system interface.<br />

Note<br />

After termination of the hardware test the device will reboot. Thereby, all annunciation buffers are erased. If<br />

required, these buffers should be extracted with DIGSI prior to the test.<br />

The hardware test can be carried out using DIGSI in the Online operating mode:<br />

• Open the Online directory by double-clicking; the operating functions for the device appear.<br />

• Click on Test; the function selection appears in the right half of the window.<br />

• Double-click in the list view on Device inputs and outputs. The dialog box with this name is opened<br />

(see Figure 3-30).<br />

<strong>SIPROTEC</strong>, 7UT6x, Manual<br />

C53000-G1176-C230-2, Release date 06.2012