Mounting and Commissioning<br />

3.3 Commissioning<br />

Test of the Output Relays<br />

416<br />

Each individual output relay can be energized allowing a check of the wiring between the output relay of the<br />

7UT6x and the plant, without having to generate the message that is assigned to the relay. As soon as the first<br />

change of state for any of the output relays is initiated, all output relays are separated from the internal device<br />

functions, and can only be operated by the hardware test function. This means, that e.g. a TRIP command<br />

coming from a protection function or a control command from the operator panel to an output relay cannot be<br />

executed.<br />

Proceed as follows in order to check the output relay:<br />

• Make sure that the switching operations caused by the output relays can be executed without any danger<br />

(see above under DANGER!).<br />

• Each output relay must be tested via the corresponding Scheduled field of the dialog box.<br />

• Finish the testing (see margin heading below „Exiting the Procedure“), so that during further testings no<br />

unwanted switchings are initiated.<br />

Test of the Binary Inputs<br />

Test of the LEDs<br />

Updating the Display<br />

To test the wiring between the plant and the binary inputs of the 7UT6x the condition in the system which<br />

initiates the binary input must be generated and the response of the device checked.<br />

To do so, open the dialog box Hardware Test again to view the physical position of the binary input. The<br />

password is not yet required.<br />

Proceed as follows in order to check the binary inputs:<br />

• Each state in the system which causes a binary input to pick up must be generated.<br />

• Check the reaction in the Status column of the dialog box. To do this, the dialog box must be updated. The<br />

options may be found below under the margin heading „Updating the Display“.<br />

• Finish the test sequence (see margin heading below „Exiting the Procedure“).<br />

If, however, the effect of a binary input must be checked without carrying out any switching in the system, it is<br />

possible to trigger individual binary inputs with the hardware test function. As soon as the first state change of<br />

any binary input is triggered and the password No. 6 has been entered, all binary inputs are separated from the<br />

system and can only be activated via the hardware test function.<br />

The light-emitting diodes (LEDs) may be tested in a similar manner to the other input/output components. As<br />

soon as the first state change of any LED has been triggered, all LEDs are separated from the internal device<br />

functionality and can only be controlled via the hardware test function. This means e.g. that no LED is<br />

illuminated anymore by a protective function or by pressing the LED reset button.<br />

When the dialog box Hardware Test is opened, the present conditions of the hardware components at that<br />

moment are read in and displayed.<br />