04.06.2013 Views

1 2 3 4 A - SIPROTEC

1 2 3 4 A - SIPROTEC

1 2 3 4 A - SIPROTEC

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

Functions<br />

2.2 Differential Protection<br />

106<br />

All following considerations are based on the convention that all currents flowing into the protected zone are<br />

defined as positive unless explicitly stated otherwise.<br />

Basic Principle with more than Two Sides<br />

Current Restraint<br />

For protected objects with three or more sides or for busbars, the differential principle is expanded in that the<br />

total of all currents flowing into the protected object is zero in healthy operation, whereas in case of a fault the<br />

total in-flowing current is equal to the fault current.<br />

See figure 2-18 as an example for four feeders. The three-winding transformer in figure 2-19 has 4 measuring<br />

locations, so it is treated by the differential protection like a „4-winding“ transformer.<br />

Figure 2-18 Basic principle of differential protection for four ends (single-phase illustration)<br />

Figure 2-19 Basic principle of differential protection for 4 measuring locations — example of a three-winding<br />

power transformer with 4 measuring locations (single-phase illustration)<br />

When an external fault causes a heavy current to flow through the protected zone, differences in the magnetic<br />

characteristics of the current transformers CT1 and CT2 (figure 2-17) under conditions of saturation may cause<br />

a significant current flow through the measuring element M. If it is greater than the respective pickup threshold,<br />

the device can trip even though no fault occurred in the protected zone. Current restraint (stabilisation) prevents<br />

such erroneous operation.<br />

In differential protection systems for protected objects with two terminals, a restraining quantity is normally<br />

derived from the current difference |I 1 – I 2| or from the arithmetical sum |I 1| + |I 2|. Both methods are equal in the<br />

relevant ranges of the stabilisation characteristics. For protected objects with more than two ends, such as<br />

multi-winding transformers, busbars etc, only the arithmetical sum method is possible. The latter method is<br />

used in 7UT6x for all protected objects. The following definitions apply for 2 measuring points:<br />

a tripping or differential current<br />

I diff = |I 1 + I 2|<br />

and the stabilisation or restraining current<br />

I stab = |I 1| + |I 2|<br />

<strong>SIPROTEC</strong>, 7UT6x, Manual<br />

C53000-G1176-C230-2, Release date 06.2012

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!