04.06.2013 Views

1 2 3 4 A - SIPROTEC

1 2 3 4 A - SIPROTEC

1 2 3 4 A - SIPROTEC

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

<strong>SIPROTEC</strong>, 7UT6x, Manual<br />

C53000-G1176-C230-2, Release date 06.2012<br />

Functions<br />

2.2 Differential Protection<br />

The type 4AM5120 is recommended for summation current transformers. These transformers have different<br />

input windings which allow for summation of the currents with the ratio 2 : 1 : 3 as well as matching of different<br />

primary currents of the main CTs to a certain extent. Figure 2-48 shows the winding arrangement.<br />

The nominal input current of each summation CT must match the nominal secondary current of the connected<br />

main CT set. The output current of the summation CT (= input current of the 7UT6x) amounts to I N =0.1A at<br />

nominal conditions, with correct matching.<br />

Figure 2-48 Winding arrangement of summation and matching transformers 4AM5120<br />

Differential Current Monitoring<br />

Whereas a high sensitivity of the differential protection is normally required for transformers, reactors, and<br />

rotating machines in order to detect even small fault currents, high fault currents are expected in case of faults<br />

on a busbar so that a higher pickup threshold (above rated current) is conceded here. This allows for a<br />

continuous monitoring of the differential currents on a low level. A small differential current in the range of<br />

operational currents indicates a fault in the secondary circuit of the current transformers.<br />

When, during normal load conditions, a differential current is detected in the order of the load current of a<br />

feeder, this indicates a missing secondary current, i.e. a fault in the secondary current leads (short-circuit or<br />

open-circuit). This condition is annunciated with time delay. The differential protection is blocked at the same<br />

time.<br />

Feeder Current Guard<br />

With busbars a release of the trip command can be set if a threshold is exceeded by one of the incoming<br />

currents. The currents of each feeder are monitored for over-shooting of a set value. Trip command is allowed<br />

only when at least one of these currents exceeds a certain (settable) threshold.<br />

131

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!