Event<br />
Fault Configuration<br />
No. Fault/Alarm Text Type Action Parameter<br />
91 Pri VelFdbk Loss Configurable Note: See option<br />
module for config<br />
parameter number<br />
<strong>PowerFlex</strong> 750-Series <strong>Install</strong>ation Instructions – Publication 750-IN001C-EN-P – September 2009<br />
101<br />
Auto<br />
Reset Description/Action(s)<br />
A Feedback Loss has been detected for the source of P134<br />
[Aux Vel Feedback]. This could be due to a problem detected<br />
by the feedback option module selected by P125 [Pri Vel<br />
Fdbk Sel] or due to a loss in communication between the<br />
feedback option module and main control board. The source<br />
of primary velocity feedback must be configured not to fault if<br />
the feedback loss switchover feature is used.<br />
93 Hw Enable Check Resettable Coast Hardware enable is disabled (jumper installed) but indicates<br />
Fault<br />
not enabled.<br />
94 Alt VelFdbk Loss Configurable Note: See option<br />
A Feedback Loss has been detected for the source of P128<br />
module for config<br />
[Alt Vel Fdbk Sel]. This could be due to a problem detected<br />
parameter number<br />
by the feedback option module selected by P128 [Alt Vel<br />
Fdbk Sel] or due to a loss in communication between the<br />
feedback option module and main control board.<br />
95 Aux VelFdbk Loss Configurable A Feedback Loss has been detected for the source of P132<br />
[Aux Vel Fdbk Sel]. This could be due to a problem detected<br />
by the feedback option module selected by P132 [Aux Vel<br />
Fdbk Sel] or due to a loss in communication between the<br />
feedback option module and main control board.<br />
96 PositionFdbkLoss Configurable A Feedback Loss has been detected for the source of P847<br />
[Psn Fdbk]. This could be due to a problem detected by the<br />
feedback option module selected by P135 [Mtr Psn Fdbk<br />
Sel] or due to a loss in communication between the feedback<br />
option module and main control board.<br />
97 Auto Tach Switch Resettable Coast Indication that either of the two following conditions exists.<br />
Fault<br />
• Tach switch has occurred and alternate feedback device<br />
has failed.<br />
• Tach switch has not occurred, Auto Tach Switch Option is<br />
enabled and both primary and alternate devices have<br />
failed.<br />
100 Parameter Chksum Resettable Coast The checksum read from the non-volatile storage does not<br />
Fault<br />
match the checksum calculated. Data set to default value.<br />
104 Pwr Brd Checksum Non-Reset<br />
The checksum read from the non-volatile storage does not<br />
Fault<br />
match the checksum calculated. Data set to default value.<br />
106 Incompat MCB-PB Non-Reset Coast The main control board did not recognize the power<br />
Fault<br />
structure. Flash with newer Application version.<br />
107 Replaced MCB-PB Resettable Coast The main control board was moved to a different power<br />
Fault<br />
structure. Data set to default values.<br />
108 Anlg Cal Chksum Non-Reset Coast The checksum read from the analog calibration data does<br />
Fault<br />
not match the checksum calculated.<br />
111 PwrBd Invalid ID Non-Reset Coast Power structure ID invalid. Flash with newer Application<br />
Fault<br />
version.<br />
112 PwrBd App MinVer Resettable Coast Power structure needs newer Application version. Flash with<br />
Fault<br />
newer Application version.<br />
113 Tracking DataErr Resettable<br />
Fault<br />
Coast Internal data error.<br />
115 PwrDn Table Full Resettable<br />
Fault<br />
Coast Internal data error.<br />
116 PwrDnEntry2Large Resettable<br />
Fault<br />
Coast Internal data error.<br />
117 PwrDn Data Chksm Resettable<br />
Fault<br />
Coast Internal data error.<br />
118 PwrBd PwrDn Chks Resettable<br />
Fault<br />
Coast Internal data error.<br />
124 App ID Changed Resettable<br />
Fault<br />
Coast Application Firmware changed. Verify Application version.<br />
125 Using Backup App Resettable<br />
Fault<br />
Coast Application did not flash correctly. Reflash.<br />
134 Start On PowerUp Alarm 1 When P345 [Start At PowerUp] is enabled, an alarm will be<br />
set for the time programmed in P346 [PowerUp Delay].