Power Jumper Wire Removal and Storage<br />
Frames 6…7 use jumper wires to complete an electrical connection when<br />
installed. <strong>Install</strong> or remove jumper wires according to the recommendations<br />
in Table 21.<br />
!<br />
ATTENTION: Hazard of equipment damage exists if jumpers<br />
are not properly disconnected. For Frames 6…7, secure the<br />
disconnected jumper wire to the standoff provided.<br />
Figure 33 Frame 6 Jumper Wire Locations<br />
When jumper wires are connected:<br />
Connected<br />
Common Mode<br />
Recommended torque (screws and nuts) = 1.36 N m (12.0 lb in)<br />
Recommended hex socket = 7 mm<br />
Recommended screwdriver = T20 Hexalobular<br />
<strong>PowerFlex</strong> 750-Series <strong>Install</strong>ation Instructions – Publication 750-IN001C-EN-P – September 2009<br />
MOV<br />
Disconnected