Drive, Fuse & Circuit Breaker Ratings<br />
Table 19 and Table 20 provide drive ratings (including continuous, 1 minute<br />
and 3 second) and recommended AC line input fuse and circuit breaker<br />
information. Sizes listed are the recommended sizes based on 40 degree C<br />
and the U.S N.E.C. Other country, state or local codes may require different<br />
ratings.<br />
Refer to Table 18 which describes input device requirements based on<br />
physical installation choice.<br />
Table 18 Input Device Requirements<br />
Enclosure<br />
UL Certification Not<br />
Frames Catalog Code Enclosure Type <strong>Install</strong>ation Type UL Certification Required Required<br />
N<br />
F<br />
IP20<br />
NEMA/UL Open Type<br />
Flange<br />
<strong>Install</strong>ed in a non-ventilated<br />
cabinet. Heat sink is inside or<br />
outside of cabinet.<br />
All devices in Table 19 are<br />
acceptable.<br />
2, 3, 4, 5 N<br />
IP20<br />
NEMA/UL Open Type<br />
<strong>Install</strong>ed outside of cabinet<br />
using NEMA Type 1 kit or in a<br />
Devices in Table 19 excluding<br />
time delay fuses and maximum<br />
F Flange<br />
ventilated cabinet.<br />
value for non-time delay fuses.<br />
G<br />
IP54<br />
NEMA/UL Type 12<br />
<strong>Install</strong>ed inside or outside of<br />
any cabinet.<br />
<strong>Install</strong>ed in any cabinet.<br />
All devices in Table 19 are<br />
acceptable.<br />
All devices in Table 19 are<br />
acceptable.<br />
6, 7<br />
N<br />
IP00<br />
NEMA/UL Open Type<br />
Heat sink is inside or outside<br />
of cabinet.<br />
<strong>Install</strong>ed outside of cabinet<br />
using NEMA Type 1 kit.<br />
All devices in Table 19 are<br />
acceptable.<br />
G<br />
IP54<br />
NEMA/UL Type 12<br />
<strong>Install</strong>ed inside or outside of<br />
any cabinet.<br />
All devices in Table 19 are<br />
acceptable.<br />
Fusing<br />
For optimum protection, semiconductor type fusing is recommended.<br />
For general purpose fusing, refer to the recommended types listed below.<br />
IEC – BS88 (British Standard) Parts 1 & 2 (1) , EN60269-1, Parts 1 & 2,<br />
type gG or equivalent should be used.<br />
UL – UL Class CC, T, RK1 or J should be used.<br />
(1) Typical designations include, but may not be limited to the following; Parts 1 & 2: AC, AD, BC, BD, CD, DD ED,<br />